The ScanCom protocol implementation supports item names. Items available in the ScanCom device are one of four different types: General, System, FRDM and Hardware.

General Items (All Models)

Item

Data Type

Description

DemandGCUpload

UI1

Demand GC Upload. Enter the run number to access after the /.

Example:  DemandGCUpload/1.

LastAlarmRecord

Date

Timestamp of the latest Alarm record collected from the device.

LastChangeLogRecord

Date

Timestamp of the latest Change Log record collected from the device.

LastDailyRecord/n

Date

Timestamp of the latest Daily Upload record collected from Meter n.

LastDemandGCRecord

Date

Timestamp of the latest Demand GC record collected from the device.

LastDLogRecord/n

Date

Timestamp of the latest DLog record collected from DLog n.

LastEventRecord

Date

Timestamp of the latest Event record collected from the device.

LastHourlyRecord/n

Date

Timestamp of the latest Hourly Upload record collected from Meter n.

LastTimeSync

Date

Timestamp of the last time sync.

LastTimeSyncResult

I4

Result code for the last time sync: 0 for no error or alarm.  Error and alarm result code values are set in the Time Sync object.

MoveHourly

UI4

Move Hourly Upload position pointer.

TimeSync

I2

Synchronize Time

System Items (All Models)

Item

Access

Data Type

Scancom ID and Description

Bat_Voltage

Read Only

R4

(0006) Input battery voltage.

Board_ID

Read Only

BSTR

(0004) Scanner board ID number. 

Cert_TimeDate

Read Only

DATE

(000F) Certification date time stamp. 

CFG_lock_status

Read Only

UI1

(001D) CFG lockout status

Charge_Voltage

Read Only

R4

(0008) Input battery charge voltage

FR_Check_alarm_cfg

Read/Write

UI1

(0018) Flow run check alarm

configuration. Bit 0 = Log in event log.  Bit 1 = Show in network alarms & alarm page.

Gas_Day

 Read/Write

I2

 (0007) Indicates the gas day hour based on contract hour. 0 - 23

HW_Range_alarm_cfg

Read/Write

UI1

(0017) Hardware range alarm configuration.   Bit 0 = Log in event log.  Bit 1 = Show in network alarms & alarm page.

Low_Bat_Dband

Read/Write

R8

(0012) Low battery alarm dead band.

Low_Bat_Limit

Read/Write

R8

(0011) Low battery alarm set point.

Low_Battery_AlStat

Read Only

UI2

(0013) Low battery alarm status

Meas_Change_Cnt

Read Only

UI2

(0022) Measurement change counter.

Model_No

Read Only

UI2

(0001) The scanner model number. 

Node_name

Read/Write

BSTR

(0005) Unit node name.

Num_Runs

Read Only

UI1

(0021) Number of flow runs in use in the device. 

NVRAM_Voltage

Read Only

R4

(000E) NVRAM backup battery voltage. 

Pwr_Save_Mode

Read/Write

UI1

(0060) Power save mode.  0 = Full power.  1 = Conserve power.

Serial_No

Read Only

BSTR

(0003) Unit serial number. 

Soft_Ver

Read Only

BSTR

(0002) Software version. 

Stn_No

Read Only

UI2

(0020) Station number. 

Superboot_flag

Read Only

UI1

(0000) Super boot flag 0/1. 0 = Normal.  

1 = Super Boot Mode

System_AlStat

Read Only

UI2

(0019) System alarm page status 0/1

TimeDate

Read Only

DATE

(0010) Device time.

Uchg_lock_bytes

Read Only

UI2

(001E) Change lock bytes.

Unit_Temp

Read Only

R4

(0009) Ambient unit temperature. 

Unit_Vref

Read/Write

R8

(000A) ATOD System Voltage Reference

UserChg_No

Read Only

UI2

(0023) Last User Change number

UserChg_Size

Read Only

UI2

(002D) User change log size in bytes.

Hardware Items General

Hardware items use the .XX/X modifiers to specify the resource parameter and slot number to access. Resource parameters should be converted from HEX to a decimal number. 

Example: HardwareAnalogInput01.16/1 would access HEX parameter 10 on slot 1 for item HardwareAnalogInput01.

Hardware Items (1130 Model)

Item

Data Type

Access

Scancom ID (HEX)

Description

AnalogIn1_0x0505

R8

Read/Write

0x0505

Analog Input #1 (A05)

AnalogIn2_0x0506

R8

Read/Write

0x0506

Analog Input #2 (A06)

AnalogIn3_0x0507

R8

Read/Write

0x0507

Analog Input #3 (A07)

AnalogIn4_0x0508

R8

Read/Write

0x0508

Analog Input #4 (A08)

AnalogIn5_0x0509

R8

Read/Write

0x0509

Analog Input #5 (A09)

AnalogIn6_0x050A

R8

Read/Write

0x050A

Analog Input #6 (A10)

Status1_0x010D

R8

Read/Write

0x010D

Status Input #1 (A13)

Status2_0x010E

R8

Read/Write

0x010E

Status Input #2 (A14)

StatusInDI01_0x0101

R8

Read/Write

0x0101

Status Input  (X01)

StatusInCD01x2_0x0102

R8

Read/Write

0x0102

Status Input  (X02)

StatusInCD01x3_0x0103

R8

Read/Write

0x0103

Status Input  (X03)

StatusInCD01x4_0x0104

R8

Read/Write

0x0104

Status Input  (X04)

StatusInCD01x5_0x0105

R8

Read/Write

0x0105

Status Input  (X05)

PulseInputX01_0x0301

R8

Read/Write

0x0301

Pulse Input (X01)

PulseInputX02_0x0302

R8

Read/Write

0x0302

Pulse Input (X02)

PulseIn1_0x0304

R8

Read/Write

0x0304

Pulse Input #1 (A04)

PulseIn2_0x030B

R8

Read/Write

0x030B

Pulse Input #2 (A11)

Hardware Items (1131 Model)

Item

Data Type

Access

Scancom ID (HEX)

Description

AnalogIn1_0x050F

R8

Read/Write

0x050F

Analog Input #1 (A15)

AnalogIn2_0x0511

R8

Read/Write

0x0511

Analog Input #2 (A17)

AnalogIn3_0x0513

R8

Read/Write

0x0513

Analog Input #3 (A19)

AnalogIn4_0x0515

R8

Read/Write

0x0515

Analog Input #4 (A21)

AnalogIn5_0x0517

R8

Read/Write

0x0517

Analog Input #5 (A23)

AnalogIn6_0x0519

R8

Read/Write

0x0519

Analog Input #6 (A25)

AnalogIn7_0x0510

R8

Read/Write

0x0510

Analog Input #7 (A16)

AnalogIn8_0x0512

R8

Read/Write

0x0512

Analog Input #8 (A18)

AnalogIn9_0x0514

R8

Read/Write

0x0514

Analog Input #9 (A20)

AnalogIn10_0x0516