Modbus OMNI Commands

Modbus OMNI Commands

Common Commands

See Device Object Common Commands for commands that are common to all device types.

Commands

Command

Description

Parameters

Command

Description

Parameters

Test Communication

When executed, ACM will poll a known OPC item from the device and wait for the response to see if the communication is good.

None

Retrieve History

Requests the retrieval of history records (for all enabled meters).

None

Retrieve meter config during next history poll

Retrieves meter configuration data during the next history retrieval

None

Reset Archive

Clears the archive retrieval position so retrieval starts at the oldest record.  Provide the meter number in parameter one, or leave blank for all meters.

Archive Number

Move Archive

Moves the saved archive retrieval position to an older record.  Provide the meter number in parameter one, or leave blank for all meters.  Enter the number of records to move back.

Archive Number

Record Count

Skip Archive

Moves the saved daily retrieval position forward.  Provide the record count in parameter one, or leave blank for all meters.  Enter the number of records to skip.

Archive Number

Reset Archive

Time Sync

Causes a comparison of the date and time in the device to the host date and time. Once compared, the configured rules of the selected time sync object will be applied - including time zone and daylight saving options.

None

Request Batch Report

Request one of the available batch text reports.  Enter the report number (1 = most recent; 8 = oldest) or leave blank for the most recent report.

Report Number

Request Prove Report

Request one of the available prove reports.  Enter the report number (1 = most recent; 8 = oldest) or leave blank for the most recent report.

Report Number

Request Daily Report

Request one of the available daily text reports.  Enter the report number (1 = most recent; 8 = oldest) or leave blank for the most recent report.

Report Number

Request Snapshot Report

Request the snapshot report.

None

Request Product File Report

Request the product report.

None

Request Status Report

Request the status report.

None

Request Last Local Snapshot report

Request the last local snapshot report.

None

Request Alarm Report

Request the alarm report. Enter the number of recent alarms to retrieve with the range 1 - 100 records or leave blank to request the last 25 alarms.

Record Count

Request Audit Trail Report

Request the audit trail report. Enter the number of recent audit trail records to retrieve with the range 1 - 100 records or leave blank to request the last 25 records.

Record Count

Request Monthly Report

Request the monthly report. This report is only available on OMNI devices with liquid firmware.

None

Read Custom Packet Configuration

Re-read the custom packet configuration from the OMNI.

None

Read Archive Configuration

Re-read the archive configuration from the OMNI. Use this command to make ACM read the configuration of one or more OMNI archives. Note that this command is sent automatically if ACM detects that the data size of an archive record does not match the size reported in a previous archive configuration read.

None

Reset Report

Reset the positions for auto-report collection.

None

Read Product Information

Re-read the product names and data from the OMNI.

None

Document Periodic Register

Write the internal register map used for periodic records to the server machine file "C:\ProgramData\AutoSol\CommunicationManager\7\asiMODBUS_OMNI_PERIODIC_REGISTER_DOC.txt"

None

Document Batch Register

Write the internal register map used for batch records to the server machine file "C:\ProgramData\AutoSol\CommunicationManager\7\asiMODBUS_OMNI_BATCH_REGISTER_DOC.txt"

None

Document Prove Register

Write the internal register map used for prove records to the server machine file "C:\ProgramData\AutoSol\CommunicationManager\7\asiMODBUS_OMNI_PROVE_REGISTER_DOC.txt"

None