Ethernet Tab
Primary/Secondary Use BSAP Ethernet
Default = Not selected. Select this option if communicating with a BSAP RTU through its Ethernet port.
Primary/Secondary Use UDP BSAP Connection
Select to indicate that the port will be using a UDP port as its BSAP connection.
Primary/Secondary Use Standard header
Use the standard header instead of the extended IBP header. The standard header does not include the IP address.
Primary/Secondary BSAP Sub Packets
Maximum sub-packets in a IBP packet (1-4).
Time Sync IP Address 1 & 2
The IP addresses on which to monitor the Time Sync port.
Time Sync Port
Port used to receive Time Sync messages from the RTU.
Be certain the firewall allows incoming UDP connections on this port. Time synchronizations using the BSAP Ethernet protocol are handled differently from those of other protocols. For ACM to successfully perform a BSAP Ethernet time sync, follow the configuration directions here.
Packetizing Delay
After the first sub-packet is ready to send, this is the amount of time in milliseconds the RTU will wait for additional sub-packets before sending the packet.
Alarm IP
The IP address to which the RTU should send alarm notifications.
As ACM does not currently support alarm notifications, it is not recommended to use the ACM Host computers IP address.
RBE IP
The IP address to which the RTU should send RBE notifications.
As ACM does not currently support RBE notifications, it is not recommended to use the ACM Host computers IP address.