See the DNP3 Configuration for information regarding Time Sync confirmation for the DNP3 device family.

Archive Collection Tab

Image Modified

Collection Interval

Select the desired collection interval relating to the Schedule object assigned on the Connection tab. EFM upload collections occur on the frequency of this interval.

Info
titleNote

If multiple schedule objects are selected for this device (Primary, Secondary, or Alternate) ensure that each Schedule has the same interval numbers configured.

...

Default = Not selected. Log fields of archive records as uploads are collected.

Archive SettingsTab

Image Modified

Collect Events

Default = Not selected. Select to collect events and configure event limits and event map.

Event Limits (Optional)

Click Image Modified to select or create an Archive Limits object for the event archive. See the Archive Limits section for more details. If no Archive Limits object is assigned, a default Type Name of "Event" will be used for the archive.

Event Map (Optional)

Click Image Modified to select or create a EFM Event Configuration. See the EFM Event Configuration section for more details.  If no Event Map object is assigned, events will be published only to the Generic meter, and to EFM formats only as string events.

...

Info
titleMultiple FLOWCAL Events

DNP3 FBx also supports publishing a single FBx parameter change event as multiple FLOWCAL events. For example, the pressure unit parameter of a Station object in the FB3000 determines the atmospheric pressure units, the base pressure units, and the static pressure units, each of which has its own FLOWCAL change event.

For each additional FLOWCAL event required, an extra event configuration record should be added to the EFM Event Configuration. The Data Source for an FBx parameter change event will always have the format "OBJECT_X.PARAMETER=0" or "OBJECT_X-Y.PARAMETER=0". The extra event configuration records in the EFM Event Configuration will each increase the number at the end of the Data Source by 1. The Field Identifiers of these records should be set to the different FLOWCAL parameters.

For the pressure unit example, the event configuration records would be:

Data Source is Station_1.PRESS_UNITS=0, Field Identifier is AtmosphericPressureUnits
Data Source is Station_1.PRESS_UNITS=1, Field Identifier is BasePressureUnits
Data Source is Station_1.PRESS_UNITS=2, Field Identifier is StaticPressureUnits

Publish Unmapped Events to All Meters

Default = Not selected. Select to publish any events that are not in the Event Map (or all events if the Event Map is Unassigned) to all meter runs instead of only to the Generic meter.

Collect Alarms

Default = Not selected. Select to collect alarms and configure alarm limits and alarm map.

Alarm Limits (Optional)

Click Image Modified to select or create an Archive Limits object for the alarm archive. See the Archive Limits section for more details.  If no Archive Limits object is assigned, a default Type Name of "Alarm" will be used for the archive.

Alarm Map (Optional)

Click Image Modified to select or create a EFM Alarm Configuration. See the EFM Alarm Configuration section for more details.  If no Alarm Map object is assigned, alarms will be published only to the Generic meter, and to EFM formats only as string alarms.

When setting up the EFM Alarm Configuration object, use the station number as the Run Number for station meters (1 for Station 1, 2 for Station 2, etc.), and 100 as the Run Number for the Generic meter. For the Data Source, use the value from the AlarmSource field when the alarm record is published to CSV.

Info
titleObject Instance Mapping

For DNP3 FBx, a single alarm configuration record in the EFM Alarm Configuration can be used to publish every alarm from an FBx object instance to a specified meter run. The Data Source must have the format "OBJECT_X=M" or "OBJECT_X-Y=M", where OBJECT_X or OBJECT_X-Y are FBx object instances. For example, if the Data Source is set to "Station_1=M", all alarms with AlarmSource fields starting with "Station_1" will be published to the Run Number (or All Meter Runs) that is configured.

Publish Unmapped Alarms to All Meters

Default = Not selected. Select to publish any alarms that are not in the Alarm Map (or all alarms if the Alarm Map is Unassigned) to all meter runs instead of only to the Generic meter.

Collect User Periodic 1/2

Default = Not selected. Select to collect the upload and configure archive object used in collectionUser Periodic records will be published to the Generic meter.

User 1/2 Archive (Optional)

Click Image Modified to select or create a Configurable Archive. See the Configurable Archive section for more details.  If no Configurable Archive object is assigned, a default Type Name of "User 1" or "User 2" and a default Time Period of 1 minute will be used for the archive.

Assigning an Archive Field Configuration to the Configurable Archive object is optional.  If an Archive Field Configuration object is assigned, the settings on the Date/Time tab will not be used, and neither will the Data Type or Byte/Word/DWord Order properties of the Archive Field Configuration records. This information is included in the history records read from the device. Units are also included in history records, but ACM doesn't support all the unit types that FBx devices can be configured for. If a history field in your FBx device is configured for a unit type that ACM doesn't support, you'll have to use the Unit Identifier and Scale String properties in the Archive Field Configuration record for that field to convert the value to a unit type that ACM does support.

...

Select the meter run (Generic, Staion Station 1, Station 2, etc.) for which to configure the following settings:

Meter

Click Image Modified to select or create the Meter object assigned to the selected meter run. See the Meter section for more details. Assigning a Meter Configuration to the Meter is optional, but if selected, both standard DNP3 object items and Emerson tunnel parameter items may be used as addresses in the Meter Configuration object.

GC Write Config

Click Image Modified to select or create the Gas Chromatograph assigned to the selected meter run. See the Gas Chromatograph section for more details.

Collect Hourly/Daily/Weekly/Monthly

Default = Not selected. Select to collect and configure archive object used in collection.

Hourly/Daily/Weekly/Monthly Archive (Optional)

Click Image Modified to select or create a Configurable Archive object. See the Configurable Archive section for more details. If no Configurable Archive object is assigned, history records can only be published to non-EFM formats, and these defaults will be used for the Type Name and Time Period of the archive:

...