Daniels RTU/ASCII Default Registers

Daniels RTU/ASCII Default Registers

Bits

Property

Default

Property

Default

Name

Bits

Base address

1001

Data Type

Single Bit

High Register

3000

Low Register

1001

Max Per Request

2000

Multi-write Code

15

Read Code

1

String Type Length

1

Write Code

5

Read-only

False

Perform single register writes

False

Always use multi-write function code

False

Subtract 1 from register address

False

High/low byte order

True

High/low word order

True

High/low dword order

True

Short Integers

Property

Default

Property

Default

Name

Short Integers

Base address

3001

Data Type

16-bit integers

High Register

5000

Low Register

3001

Max Per Request

125

Multi-write Code

16

Read Code

3

String Type Length

1

Write Code

6

Read-only

False

Perform single register writes

False

Always use multi-write function code

False

Subtract 1 from register address

False

High/low byte order

True

High/low word order

True

High/low dword order

True

Long Integers

Property

Default

Property

Default

Name

Long Integers

Base address

5001

Data Type

32-bit integer

High Register

7000

Low Register

5001

Max Per Request

60

Multi-write Code

16

Read Code

3

String Type Length

1

Write Code

6

Read-only

False

Perform single register writes

False

Always use multi-write function code

False

Subtract 1 from register address

False

High/low byte order

True

High/low word order

True

High/low dword order

True

Floats

Property

Default

Property

Default

Name

Floats

Base address

7001

Data Type

32-bit floating point

High Register

9999

Low Register

7001

Max Per Request

60

Multi-write Code

16

Read Code

3

String Type Length

1

Write Code

6

Read-only

False

Perform single register writes

False

Always use multi-write function code

False

Subtract 1 from register address

False

High/low byte order

True

High/low word order

True

High/low dword order

True

Related content

Modbus RTU/ASCII Default Registers
Modbus RTU/ASCII Default Registers
More like this
Enron Default Registers
Enron Default Registers
More like this
Omni Default Registers
Omni Default Registers
More like this
BenchMark RTU Configuration
BenchMark RTU Configuration
More like this
Modbus Register Record
Modbus Register Record
More like this
AutoPILOT Pro Default Registers
AutoPILOT Pro Default Registers
More like this

For assistance, please submit a ticket via our Support Portal, email autosol.support@autosoln.com or call 281.286.6017 to speak to a support team member.