Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 6 Next »

Property

Description

Name

The name of this item

Enabled

If checked the Edge ACM will poll this device when running

ROC Series

The type of ROC you wish to poll:

  • REGFLO

  • Floboss 100 Series & FBx

  • ROC 300 ROCPAC

  • ROC 300 FLASHPAC

  • ROC 407

  • Floboss 503

  • Floboss 504

  • ROC 800 Series

Publish Rate

The time, in milliseconds, between Device Data Messages

Alter Publish Rate on Point Limits

If enabled, tag limits are monitored by the publisher and the publisher will switch to the Altered Publish Rate if any tag is out of limits

Altered Publish Rate

The time, in milliseconds, between Device Data Messages if any tags assigned to this device are out of limits (Limits are set on the tag object)

ROC Unit

Sets the ROC Unit Address, valid values 0-255

ROC Group

Sets the ROC Group Address, valid values 0-255

Host Unit

Sets the Host Unit Address, valid values 0-255

Host Group

Sets the Host Group Address, valid values 0-255

Max Message Length

Sets a limit on the maximum number of bytes to send in a single message to the End Device, valid values 8-240

Read User Opcode Data Via Opcode 10

This option causes eACM to read user opcode points using ROC protocol opcode 10 instead of opcode 180.  This can be a more efficient way to read user opcode points, as long most of the requested points are continuous.  If there are many gaps between requested user opcode points, then this option may not be desirable, as gaps will cause items to be polled in separate reads.  This option is sometimes required to read user opcode data sourced from a user program running the ROC device that cannot be read with opcode 180.

Tag Group

The Tag Group that is associated with this device. Edge ACM will only poll this device for the tags in this group

Connection Settings

The object that contains the connection settings Edge ACM will use to connect to the End Device

Folder

The parent folder for this item

  • No labels