Corrective Action: You must create and assign an archive object for each type of upload you want your Romet device to collect. 

Scenario #5: Audit upload does not work correctly, or published data is incorrect, after making audit configuration changes on the RTU.

Problem: Audit upload publish data is incorrect or incomplete.

Meaning: ACM reads the device's audit configuration and publishes data based upon internally stored data tables. Because of a configuration change on the RTU, ACM and the device are not in sync.

Corrective Action: On the Command tab of the device in ACM, issue the 'Retrieve Audit Log Config During Next History Poll' command. Next issue the 'Move Audit Pointer Back' command and select the time of the last known good record, or issue 'Reset Audit Pointer' if no good records have been uploaded. Issue the command to 'Retrieve History'.

Scenario : Item's OPC status is 'Bad - Configuration Error'

Problem: No data is returned for item after polling.

...