A UDP Receive Port must be specified and must be the same as the IBP Port configured in the BSAP device. This port number should also be used as the TCP/IP connection's main port number. ControlWave devices default to UDP port 1234, and it's very uncommon for this default to be changed.

For instructions on how to You can confirm the value of a BSAP device's IBP Port using OpenBSI, see the attached PDF file..  The screen capture below is taken from OpenBSI Netview V5.6 and shows the Ethernet communication settings of the BSAP device. To get to this screen, right click on the device in Netview, select RTU | RTU Configuration Parameters, and click the Load From RTU button.

Image Added

ACM UDP BSAP Connection Type

...