Physical location numbers in the ROC unit begin at one (1), whereas physical location numbers for the ROC protocol in ACM are zero-based and begin at zero (0). The Physical location can be found when configuring the RTU in ROCLINK, and can be related to the meter run number or can be displayed in ROCLINK as “Point Number”. Point number will be displayed in ROCLINK in one of two ways, but when used with ACM, it will need to be converted into its decimal equivalent. The screenshots and tables below indicate where to find the Point Number and the definition of the conversions.Point Number in ROCLINK
The Point number can be found on this display in ROCLINK:

In order to see TLPs in ROCLink, you must toggle on an option under the "Tools" menu:


Image Added

Converting Point Number to decimal equivalent

...

ItemData TypeDescriptionT.P:L

DO.POINT_TAG_ID:n

STRING

 10 character name for the discrete output.

2.0:n

DO.TIME_ON:n

UI2

Number of 50 msec. intervals the output is on.

2.1:n

DO.SPARE_1:n

UI1

Parameter number 2. Not Used.  READ ONLY.

2.2:n

DO.STATUS:n

UI1

The current state of the output.

2.3:n

DO.MODE:n

UI1

Bitmask settings for the discrete output.

•      Bit 0: Momentary (0 = Disable, 1 = Enable)

•      Bit 1: Toggle (0 = Disable, 1 = Enable)

•      Bit 2: Not Used (Do not set)

•      Bit 3: TDO Enable (1 = Timed Discrete Output, 0 = Normal)

•      Bit 4: CLR on Reset (0 = Disable, 1 =Enable)

•      Bit 5: Not Used

•      Bit 6: Not Used

•      Bit 7: Manual Mode (1 = scan disabled, 0 = Normal scan)

2.4:n

DO.ALARM_CODE:n

UI1

Bitmask settings for the discrete output.

•       Bit 0-5: Not Used

•       Bit 6: Point Fail (FloBoss 107 Only)

•       Bit 7: Manual Mode

2.5:n

DO.ACCUM_VALUE:n

UI4

Number of 0 to 1 transitions.

2.6:n

DO.UNITS:n

STRING

 10 character name for the Engineering Units.

2.7:n

DO.CYCLE_TIME:n

UI2

The sum of the on and off time (1 cycle time) in 50 msec. periods.

2.8:n

DO.0_COUNT:n

I2

The count in 50 msec. periods that represent a 0 percent output pulse width.

2.9:n

DO.100_COUNT:n

I2

The count in 50 msec. periods that represent a 100 percent output pulse width.

2.10:n

DO.LOW_READING_EU:n

R4

The EU value corresponding to the 0 percent count.

2.11:n

DO.HIGH_READING_EU:n

R4

The EU value corresponding to the 100 percent count.

2.12:n

DO.EU_VALUE:n

R4

EU value that corresponds to the amount of on-time for the discrete output.

2.13:n

DO.ALARM_MODE:nUI1

Indicates the alarm mode.

  • Bit 7 – Not Used
  • Bit 6 – Report-by-Exception (RBX) on Set. Valid values are 0 (Disabled on Set) and 1 (RBX on Set)

Note: Valid only for the FB107.

2.14:n
DO.SCAN_MODE:nUI1

Indicates scanning mode. Valid values are 0 (Automatic) and 1 (Manual).

Note: Valid only for the FB107.

2.15:n
DO.MANUAL_STATE:nUI8Manual state (FB107 only).2.16:n
DO.PHYSICAL_STATE:nUI8Physical state (FB107 only).2.17:n

Point Type 3 - Analog Input Items

ItemData TypeDescriptionT.P:L

AI.POINT_TAG_ID:n

STRING

 10 character name for the analog input.

3.0:n

AI.UNITS:n

STRING

 10 character name for the Engineering Units.

3.1:n

AI.SCAN_PERIOD:n

UI2

Time between updates in 50 msec. intervals.

3.2:n

AI.FILTER:n

UI2

Percentage of last value used in calculating current value.

3.3:n

AI.ADJUSTED_ATOD_0:n

I2

A/D value corresponding to 0 percent input.

3.4:n

AI.ADJUSTED_ATOD_100:n

I2

A/D value corresponding to 100 percent input.

3.5:n

AI.LOW_READING_EU:n

R4

EU value corresponding to 0 percent input.

3.6:n

AI.HIGH_READING_EU:n

R4

EU value corresponding to 100 percent input.

3.7:n

AI.LOW_ALARM_EU:n

R4

EU value representing the low alarm threshold.

3.8:n

AI.HIGH_ALARM_EU:n

R4

EU value representing the high alarm threshold.

3.9:n

AI.LOLO_ALARM_EU:n

R4

EU value representing the low low alarm threshold.

3.10:n

AI.HIHI_ALARM_EU:n

R4

EU value representing the high high alarm threshold.

3.11:n

AI.DELTA_ALARM_EU:n

R4

EU value representing greatest allowable change between scans before generating an alarm.

3.12:n

AI.ALARM_DEADBAND:n

R4

EU value representing a dead zone above high alarm limits and below the low alarm limits to prevent spurious alarms.

3.13:n

AI.FILTERED_EU:n

R4

The current value in engineering units.

3.14:n

AI.MODE:n

UI1

Bitmask settings for the analog input.

•         Bit 0: Not Used

•         Bit 1: Low Low and High High Clamping (0 = Disable, 1 = Enable)

•         Bit 2: Temperature Compensation (0 = Enable, 1 = Disable)

•         Bit 3: Use Average Input (0 = Disable, 1 = Enable)

•         Bit 4: ALM Enable (0 = Disable, 1 = Enable)

•         Bit 5: RBX on Clear (0 = Disable, 1 = Enable)

•         Bit 6: RBX on Set (0 = Disable, 1 = Enable)

•        Bit 7: Manual Mode (0 = Disable, 1 = Enable)

3.15:n

AI.RAW_ATOD_INPUT:n

I2

Raw A/D input reading: 

READ ONLY IN ROC 300 SERIES AND FB 407.

R/W IN FB 100 SERIES AND FB 500 SERIES.

3.17:n

AI.ACTUAL_SCAN:n

UI2

Actual scan time. Should be the same as Scan Period unless system is overloaded. 

READ ONLY.

3.18:n

AI.FAULT_EU_VALUE:n

R4

Fault EU Value

3.19:n

AI. CALIB_ZERO_RAW:n


UI2

Calibrated Zero Raw

3.20:n

AI.CALIB_MID_RAW_1:n

UI2

Calibrated Mid-point Raw #1 A/D Value

3.21:n

AI.CALIB_MID_RAW_2:n

UI2

Calibrated Mid-point Raw #2 A/D Value

3.22:n

AI.CALIB_MID_RAW_3:n

UI2

Calibrated Mid-point Raw #3 A/D Value

3.23:n

AI.CALIB_SPAN_RAW:n

UI2

Calibrated Span Raw

3.24:n

AI.CALIB_ZERO_EU_VALUE:n

R4

Calibrated Zero EU Value

3.25:n

AI.CALIB_MID_EU_VALUE_1:n

R4

Calibrated Mid-point EU #1

3.26:n

AI.CALIB_MID_EU_VALUE_2:n

R4

Calibrated Mid-point EU #2

3.27:n

AI.CALIB_MID_EU_VALUE_3:n

R4

Calibrated Mid-point EU #3

3.28:n

AI.CALIB_SPAN_EU:n

R4

Calibrated Span EU

3.29:n

AI.OFFSET_ADDED_CALC_EU:n

      R4

Offset to be added to all calculated EU fields

3.30:n

AI_CALIB_SET_VALUE_ED:n

R4

Calibrated set value; desired ED value for a calibrated point

3.31:n

AI_CALIB_MANUAL_VALUE:n

R4

Calibrated manual value; the current EU value of the AI while performing calibration

3.32:n

AI.CALIB_TIMER:n

UI2

Calibration Timer-number of seconds until a timeout occurs

3.33:n

AI.CALIB_TIMER:n

UI2

Calibration Timer-number of seconds until a timeout occurs

3.33:n

AI.CALIB_MODE:n

UI8

Calibration Mode

•       0 = Use current calibration

•       1 = Start calibration

•       2 = Calibrate input

•       3 = Restore previous calibration values

•       4 = End calibration

Note: No event is logged for this parameter

3.34:n

AI.CALIB_TYPE:n

UI8

Calibration Mode

  • 0 = No calibration active
  • 1 = Set Zero
  • 2 = Set Span
  • 3 = Set Mid-point #1
  • 4 = Set Mid-point #2
  • 5 = Set Mid-point #3
  • 6 = Set Offset

3.35:n

t

Point Type 4 - Analog Output Items

...

ItemData TypeDescriptionT.P:L

DO.POINT_TAG_ID

AC

Identification name for specific AO. Values must be printable ASCII characters.

102.0:n

DO.UNITS_TAG

AC

Describes the units used by the AO. Values must be printable ASCII characters.

102.1:n

DO.SCANNING

UINT8

If disabled, no changes to the output will occur. If in

Manual, only the user can change the values of the AO.

If in automatic, anything can change the values of the AO.

•       0 = Disabled

•       1 = Automatic

•       2 = Manual 

102.2:n

DO.ALARMING

UINT8

If enabled, alarms may be generated and sent to the Alarm Log.

•       0 = Disabled

•       1 = Enabled

102.3:n

DO.SRBX_ON_CLEAR

UINT8

Indicates a SRBX alarm is desired if an alarm condition clears

•       0 = SRBX on Clear Disabled

•       1 = SRBX on Clear Enabled.

102.4:n

DO.SRBX_ON_SET

UINT8

Indicates a SRBX alarm is desired if an alarm condition occurs.

•     0 = SRBX on Set Disabled

•     1 = SRBX on Set Enabled

102.5:n

DO.ALARM_CODE

BIN

If bit 5 is set, the Scanning (parameter #2) has been set to Manual. If clear, the Scanning (parameter #2) has been set to either Disable or Automatic

If bit 7 is set, the Scanning (parameter #2) has been disabled. If clear, the Scanning (parameter #2) has been set to either Automatic or Manual. READ ONLY.

102.6:n

DO.FAILSAFE_ON_RESET

UINT8

If enabled, the Status (parameter #8) will be set to the status indicated in ‘Failsafe Status Value’ (Parameter #22) on a restart of any kind. If disabled, the last Status before the restart will be used. 0 = Output Last Status on Reset, 1 = Use Failsafe value on Reset.

102.7:n

DO.STATUS

UINT8

Indicates what state the DO is currently in, ON (1) or OFF (0).

102.8:n

DO.ACCUM_VALUE  

UINT32

Number of times the Status (parameter #8) goes from OFF to ON.

102.9:n

DO.MOMENTARY_MODE  

UINT8

If enabled, the Status (parameter #8) will be turned ON for the entered Time On (parameter #14) and then be turned OFF. 

•       0 = Momentary Disabled

•       1 = Momentary Enabled

102.10:n

DO.MOMENTARY_ACTIVE

UINT8

Indicates that the DO currently has the Momentary ability active. 

•       0 = Momentary Not Active

•       1 = Momentary Active

102.11:n

DO.TOGGLE_MODE  

UINT8

If enabled, the Status (parameter #8) will be turned ON for the entered Time On (parameter #14) and then turned OFF for the same Time On. The Status will continue to cycle between the ON and OFF states. 

•       0 = Toggle Disabled

•       1 = Toggle Enabled

102.12:n

DO.TDO_MODE

UINT8

If enabled, the Status (parameter #8) will be turned ON for a calculated Time On (parameter #14) based upon the entered EU Value (parameter #20). After the Time On has expired, the Status will be turned OFF and remain that way until a new EU Value is entered. 

•       0 = TDO Disabled

•       1 = TDO Enabled

102.13:n

DO.TIME_ON

FLP

Number of seconds the Status (parameter #8) will be turned ON for if in TDO, Toggle, or Momentary Mode.

102.14:n

DO.CYCLE_TIME  

FLP

Number of seconds for when TDO Mode (parameter

#13) and Toggle Mode (parameter #12) are selected.

The Status (parameter #8) will be ON for the calculated

Time On (parameter #14) based upon the entered EU Value (parameter #20). The Status will then be turned OFF based upon the Cycle Time minus the Time On.

102.15:n

DO.LOW_READING_TIME

FLP

Minimum number of seconds the calculated Time On

(parameter #14) will be when the entered EU Value (parameter #20) is less than or equal to the entered Low Reading EU (parameter #18).

102.16:n

DO.HIGH_READING_TIME

FLP

Maximum number of seconds the calculated Time On

(parameter #14) will be when they entered EU Value (parameter #20) is greater than or equal to the entered High Reading EU (parameter #19).

102.17:n

DO.LOW_READING_EU

FLP

Minimum EU Value (parameter #20) possible.

102.18:n

DO.HIGH_READING_EU

FLP

Maximum EU Value (parameter #20) possible.

102.19:n

DO.EU_VALUE  

FLP

Value in Engineering Units.

102.20:n

DO.MANUAL_VALUE

UINT8

Manual Value used when Scanning (parameter #2) is in manual mode

102.21:n

DO.FAILSAFE_STATUS

UINT8

This is the status the output will be placed in when the unit is started and the Failsafe on Reset Parameter

(Parameter 7) is set to 1, Use Failsafe value on reset.

102.22:n

DO.RESERVED

FLP

Max Scan Period READ ONLY.

102.23:n

DO.PHYSICAL_OUTPUT

UINT8

Indicates the DO’s current state. Valid values are 0 (OFF) and 1 (ON).

102.24:n

Point Type 103 - ROC 800 Analog Input Items

...