Physical location numbers in the ROC unit begin at one (1), whereas physical location numbers for the ROC protocol in ACM are zero-based and begin at zero (0). The Physical location can be found when configuring the RTU in ROCLINK, and can be related to the meter run number or can be displayed in ROCLINK as “Point Number”. Point number will be displayed in ROCLINK in one of two ways, but when used with ACM, it will need to be converted into its decimal equivalent. The screenshots and tables below indicate where to find the Point Number and the definition of the conversions.Point Number in ROCLINK
The Point number can be found on this display in ROCLINK:
In order to see TLPs in ROCLink, you must toggle on an option under the "Tools" menu:
Converting Point Number to decimal equivalent
...
Item | Data Type | Description | T.P:L |
---|---|---|---|
DO.POINT_TAG_ID:n | STRING | 10 character name for the discrete output. | 2.0:n |
DO.TIME_ON:n | UI2 | Number of 50 msec. intervals the output is on. | 2.1:n |
DO.SPARE_1:n | UI1 | Parameter number 2. Not Used. READ ONLY. | 2.2:n |
DO.STATUS:n | UI1 | The current state of the output. | 2.3:n |
DO.MODE:n | UI1 | Bitmask settings for the discrete output. • Bit 0: Momentary (0 = Disable, 1 = Enable) • Bit 1: Toggle (0 = Disable, 1 = Enable) • Bit 2: Not Used (Do not set) • Bit 3: TDO Enable (1 = Timed Discrete Output, 0 = Normal) • Bit 4: CLR on Reset (0 = Disable, 1 =Enable) • Bit 5: Not Used • Bit 6: Not Used • Bit 7: Manual Mode (1 = scan disabled, 0 = Normal scan) | 2.4:n |
DO.ALARM_CODE:n | UI1 | Bitmask settings for the discrete output. • Bit 0-5: Not Used • Bit 6: Point Fail (FloBoss 107 Only) • Bit 7: Manual Mode | 2.5:n |
DO.ACCUM_VALUE:n | UI4 | Number of 0 to 1 transitions. | 2.6:n |
DO.UNITS:n | STRING | 10 character name for the Engineering Units. | 2.7:n |
DO.CYCLE_TIME:n | UI2 | The sum of the on and off time (1 cycle time) in 50 msec. periods. | 2.8:n |
DO.0_COUNT:n | I2 | The count in 50 msec. periods that represent a 0 percent output pulse width. | 2.9:n |
DO.100_COUNT:n | I2 | The count in 50 msec. periods that represent a 100 percent output pulse width. | 2.10:n |
DO.LOW_READING_EU:n | R4 | The EU value corresponding to the 0 percent count. | 2.11:n |
DO.HIGH_READING_EU:n | R4 | The EU value corresponding to the 100 percent count. | 2.12:n |
DO.EU_VALUE:n | R4 | EU value that corresponds to the amount of on-time for the discrete output. | 2.13:n |
DO.ALARM_MODE:n | UI1 | Indicates the alarm mode.
Note: Valid only for the FB107. | 2.14:n |
DO.SCAN_MODE:n | UI1 | Indicates scanning mode. Valid values are 0 (Automatic) and 1 (Manual). Note: Valid only for the FB107. | 2.15:n |
DO.MANUAL_STATE:n | UI8 | Manual state (FB107 only). | 2.16:n |
DO.PHYSICAL_STATE:n | UI8 | Physical state (FB107 only). | 2.17:n |
Point Type 3 - Analog Input Items
Item | Data Type | Description | T.P:L |
---|---|---|---|
AI.POINT_TAG_ID:n | STRING | 10 character name for the analog input. | 3.0:n |
AI.UNITS:n | STRING | 10 character name for the Engineering Units. | 3.1:n |
AI.SCAN_PERIOD:n | UI2 | Time between updates in 50 msec. intervals. | 3.2:n |
AI.FILTER:n | UI2 | Percentage of last value used in calculating current value. | 3.3:n |
AI.ADJUSTED_ATOD_0:n | I2 | A/D value corresponding to 0 percent input. | 3.4:n |
AI.ADJUSTED_ATOD_100:n | I2 | A/D value corresponding to 100 percent input. | 3.5:n |
AI.LOW_READING_EU:n | R4 | EU value corresponding to 0 percent input. | 3.6:n |
AI.HIGH_READING_EU:n | R4 | EU value corresponding to 100 percent input. | 3.7:n |
AI.LOW_ALARM_EU:n | R4 | EU value representing the low alarm threshold. | 3.8:n |
AI.HIGH_ALARM_EU:n | R4 | EU value representing the high alarm threshold. | 3.9:n |
AI.LOLO_ALARM_EU:n | R4 | EU value representing the low low alarm threshold. | 3.10:n |
AI.HIHI_ALARM_EU:n | R4 | EU value representing the high high alarm threshold. | 3.11:n |
AI.DELTA_ALARM_EU:n | R4 | EU value representing greatest allowable change between scans before generating an alarm. | 3.12:n |
AI.ALARM_DEADBAND:n | R4 | EU value representing a dead zone above high alarm limits and below the low alarm limits to prevent spurious alarms. | 3.13:n |
AI.FILTERED_EU:n | R4 | The current value in engineering units. | 3.14:n |
AI.MODE:n | UI1 | Bitmask settings for the analog input. • Bit 0: Not Used • Bit 1: Low Low and High High Clamping (0 = Disable, 1 = Enable) • Bit 2: Temperature Compensation (0 = Enable, 1 = Disable) • Bit 3: Use Average Input (0 = Disable, 1 = Enable) • Bit 4: ALM Enable (0 = Disable, 1 = Enable) • Bit 5: RBX on Clear (0 = Disable, 1 = Enable) • Bit 6: RBX on Set (0 = Disable, 1 = Enable) • Bit 7: Manual Mode (0 = Disable, 1 = Enable) | 3.15:n |
AI.RAW_ATOD_INPUT:n | I2 | Raw A/D input reading: READ ONLY IN ROC 300 SERIES AND FB 407. R/W IN FB 100 SERIES AND FB 500 SERIES. | 3.17:n |
AI.ACTUAL_SCAN:n | UI2 | Actual scan time. Should be the same as Scan Period unless system is overloaded. READ ONLY. | 3.18:n |
AI.FAULT_EU_VALUE:n | R4 | Fault EU Value | 3.19:n |
AI. CALIB_ZERO_RAW:n | UI2 | Calibrated Zero Raw | 3.20:n |
AI.CALIB_MID_RAW_1:n | UI2 | Calibrated Mid-point Raw #1 A/D Value | 3.21:n |
AI.CALIB_MID_RAW_2:n | UI2 | Calibrated Mid-point Raw #2 A/D Value | 3.22:n |
AI.CALIB_MID_RAW_3:n | UI2 | Calibrated Mid-point Raw #3 A/D Value | 3.23:n |
AI.CALIB_SPAN_RAW:n | UI2 | Calibrated Span Raw | 3.24:n |
AI.CALIB_ZERO_EU_VALUE:n | R4 | Calibrated Zero EU Value | 3.25:n |
AI.CALIB_MID_EU_VALUE_1:n | R4 | Calibrated Mid-point EU #1 | 3.26:n |
AI.CALIB_MID_EU_VALUE_2:n | R4 | Calibrated Mid-point EU #2 | 3.27:n |
AI.CALIB_MID_EU_VALUE_3:n | R4 | Calibrated Mid-point EU #3 | 3.28:n |
AI.CALIB_SPAN_EU:n | R4 | Calibrated Span EU | 3.29:n |
AI.OFFSET_ADDED_CALC_EU:n | R4 | Offset to be added to all calculated EU fields | 3.30:n |
AI_CALIB_SET_VALUE_ED:n | R4 | Calibrated set value; desired ED value for a calibrated point | 3.31:n |
AI_CALIB_MANUAL_VALUE:n | R4 | Calibrated manual value; the current EU value of the AI while performing calibration | 3.32:n |
AI.CALIB_TIMER:n | UI2 | Calibration Timer-number of seconds until a timeout occurs | 3.33:n |
AI.CALIB_TIMER:n | UI2 | Calibration Timer-number of seconds until a timeout occurs | 3.33:n |
AI.CALIB_MODE:n | UI8 | Calibration Mode • 0 = Use current calibration • 1 = Start calibration • 2 = Calibrate input • 3 = Restore previous calibration values • 4 = End calibration Note: No event is logged for this parameter | 3.34:n |
AI.CALIB_TYPE:n | UI8 | Calibration Mode
| 3.35:n |
t
Point Type 4 - Analog Output Items
...
Item | Data Type | Description | T.P:L |
---|---|---|---|
HART.CHANNEL_VERSION:n | STRING | 10 character version number for the firmware in this channel. Read only. | 85.0:n |
HART.CHANNEL_IO:n | UI1 | Indicates if channel is input (0) or output (1). Read only. | 85.1:n |
HART.COMM_MODE:n | UI1 | 0=Disabled, 1=Point to Point, 2=Multidrop. | 85.2:n |
HART.NUMBER_DEVICES:n | UI1 | Number of devices connected in multidrop mode. | 85.3:n |
HART.COMM_STATUS:n | UI1 | Communication status. 0=Not scanning, 1=Scanning normal, 2=Dual Master detected, 3=Pass thru, 4=Device in burst mode. Read only. | 85.4:n |
HART.ANALOG_MODE:n | UI1 | Analog mode. 0=Disabled, 1=Enabled. | 85.5:n |
HART.PASS_THRU:n | UI1 | Enables ROC protocol pass thru communication. 0=Disabled, 1=Enabled. | 85.6:n |
HART.PASS_THRU_TIMEOUT:n | UI4 | Timeout (in millisecons) to resume after pass thru communications. | 85.7:n |
HART.HART_EU_VALUE:n | R4 | EU value of analog input or output. Read only. | 85.8:n |
HART.HART_FAILSAFE_ON_RESET:n | UI1 | 0=Use last EU value on reset, 1=Use failsafe value on reset. | 85.9:n |
HART.HART_FAILSAFE_VALUE:n | R4 | The value outputted when the unit is started. | 85.10:n |
HART.HART_MANUAL_VALUE:n | R4 | The value used in output when scanning is in manual mode. | 85.11:n |
HART.HART_AUTO_VALUE:n | R4 | The value used in output when scanning is in auto mode. | 85.12:n |
HART.HART_PHYSICAL_VALUE:n | R4 | The current value of the output in engineering units. | 85.13:n |
HART.PHYSICAL_RAW_DA:n | UI2 | Calculated digital-to-analog value. | 85.14:n |
HART.CALIBRATION_LIVE:n | R4 | The live value when calibrating an AI | 85.15:n |
HART.CALIBRATION_ZERO:n | R4 | The zero EU calibration value | 85.16:n |
HART.CALIBRATION_SPAN:n | R4 | The span EU calibration value | 85.17:n |
HART.EU_RAW_VALUE:n | UI2 | The EU value of AI or AO. | 85.18:n |
HART.EU_RAW_CALIBRATION_ZERO:n | UI2 | The zero raw calibration value. | 85.19:n |
HART.EU_RAW_CALIBRATION_SPAN:n | UI2 | The span raw calibration value. | 85.20:n |
HART.DEVICE_1_POLL_MODE:n | UI1 | The polling mode for the device. 0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update. | 85.21:n |
HART.DEVICE_1_POLL_ADDRESS:n | UI1 | Polling address for the device. Read only. | 85.22:n |
HART.DEVICE_1_STATUS:n | UI1 | 0=no device found, 1=communication, 2=comm error. | 85.23:n |
HART.DEVICE_1_ACTUAL_SCAN_PERIOD:n | R4 | Period at which device is being updates. | 85.24:n |
HART. DEVICE_1_TAG:n | STRING | 10 character tag that resides in this device. Read only. | 85.25:n |
HART.DEVICE_1_RESPONSE_CODE:n | UI2 | Response code and status received from device. Read only. | 85.26:n |
HART.DEVICE_1_ACTIVE_ALARMS:n | UI1 | Active alarms reported by device. Read only. | 85.27:n |
HART.DEVICE_1_CURRENT:n | R4 | Current in milliamps. Read only. | 85.28:n |
HART.DEVICE_1_PERCENT_RANGE:n | R4 | Percent of range reported by device. Read only. | 85.29:n |
HART.DEVICE_1_FAILSAFE_ENABLE:n | UI1 | Enables the use of fail safe values for the dynamic variables when the unit resets. | 85.30:n |
HART.DEVICE_1_PV_UNITS:n | UI1 | Units code for primary variable reported by device. Read only. | 85.31:n |
HART.DEVICE_1_PV:n | R4 | Value of primary variable reported by device. Read only. | 85.32:n |
HART.DEVICE_1_PV_FAILSAFE:n | R4 | Primary fail safe value for device. | 85.33:n |
HART.DEVICE_1_SV_UNITS:n | UI1 | Units code for secondary variable reported by device. Read only. | 85.34:n |
HART.DEVICE_1_SV:n | R4 | Value of secondary variable reported by device. Read only. | 85.35:n |
HART.DEVICE_1_SV_FAILSAFE:n | R4 | Secondary fail safe value for device. | 85.36:n |
HART.DEVICE_1_TV_UNITS:n | UI1 | Units code for tertiary variable reported by device. Read only. | 85.37:n |
HART.DEVICE_1_TV:n | R4 | Value of tertiary variable reported by device. Read only. | 85.38:n |
HART.DEVICE_1_TV_FAILSAFE:n | R4 | Tertiary fail safe value for device. | 85.39:n |
HART.DEVICE_1_FV_UNITS:n | UI1 | Units code for fourth variable reported by device. Read only. | 85.40:n |
HART.DEVICE_1_FV:n | R4 | Value of fourth variable reported by device. Read only. | 85.41:n |
HART.DEVICE_1_FV_FAILSAFE:n | R4 | Fourth fail safe value for device. | 85.42:n |
HART.DEVICE_1_SLOT_0_ASSIGN:n | UI1 | Slot 0 variable to request from device. | 85.43:n |
HART.DEVICE_1_SLOT_0_UNITS:n | UI1 | Units of slot 0 variable to request from device. Read only. | 85.44:n |
HART.DEVICE_1_SLOT_0_VARIABLE:n | R4 | Value of slot 0 variable requested from device. | 85.45:n |
HART.DEVICE_1_SLOT_1_ASSIGN:n | UI1 | Slot 1 variable to request from device. | 85.46:n |
HART.DEVICE_1_SLOT_1_UNITS:n | UI1 | Units of slot 1 variable to request from device. Read only. | 85.47:n |
HART.DEVICE_1_SLOT_1_VARIABLE:n | R4 | Value of slot 1 variable requested from device. | 85.48:n |
HART.DEVICE_1_SLOT_2_ASSIGN:n | UI1 | Slot 2 variable to request from device. | 85.49:n |
HART.DEVICE_1_SLOT_2_UNITS:n | UI1 | Units of slot 2 variable to request from device. Read only. | 85.50:n |
HART.DEVICE_1_SLOT_2_VARIABLE:n | R4 | Value of slot 2 variable requested from device. | 85.51:n |
HART.DEVICE_1_SLOT_3_ASSIGN:n | UI1 | Slot 3 variable to request from device. | 85.52:n |
HART.DEVICE_1_SLOT_3_UNITS:n | UI1 | Units of slot 3 variable to request from device. Read only. | 85.53:n |
HART.DEVICE_1_SLOT_3_VARIABLE:n | R4 | Value of slot 3 variable requested from device. | 85.54:n |
HART.DEVICE_1_MESSAGE:n | STRING | 40 character device message. | 85.55:n |
HART.DEVICE_1_DESCRIPTION:n | STRING | 20 character device description. | 85.56:n |
HART.DEVICE_1_MANU_ID:n | UI2 | Device manufacture ID. Read only. | 85.57:n |
HART.DEVICE_1_SERIAL:n | UI4 | Device serial number. Read only. | 85.58:n |
HART.DEVICE_1_ID_NUMBER:n | UI4 | Device sensor units. Read only. | 85.59:n |
HART.DEVICE_1_SENSOR_UNITS:n | UI1 | Device sensor units. Read only. | 85.60:n |
HART.DEVICE_1_SENSOR_UPPER_LIM:n | R4 | Device sensor upper limit. Read only. | 85.61:n |
HART.DEVICE_1_SENSOR_LOWER_LIM:n | R4 | Device sensor lower limit. Read only. | 85.62:n |
HART.DEVICE_1_MINIMUM_SPAN:n | R4 | Device minimum sensor span. Read only. | 85.63:n |
HART.DEVICE_1_OUTPUT_UNITS:n | UI1 | Device output units. Read only. | 85.64:n |
HART.DEVICE_1_OUTPUT_UPPER_LIM:n | R4 | Device output upper limit. Read only. | 85.65:n |
HART.DEVICE_1_OUTPUT_LOWER_LIM:n | R4 | Device output lower limit. Read only. | 85.66:n |
HART.DEVICE_1_DAMPING_VALUE:n | R4 | Device damping value. Read only. | 85.67:n |
HART.DEVICE_2_POLL_MODE:n | UI1 | The polling mode for the device. 0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update. | 85.68:n |
HART.DEVICE_2_POLL_ADDRESS:n | UI1 | Polling address for the device. Read only. | 85.69:n |
HART.DEVICE_2_STATUS:n | UI1 | 0=no device found, 1=communication, 2=comm error. | 85.70:n |
HART.DEVICE_2_ACTUAL_SCAN_PERIOD:n | R4 | Period at which device is being updates. | 85.71:n |
HART. DEVICE_2_TAG:n | STRING | 10 character tag that resides in this device. Read only. | 85.72:n |
HART.DEVICE_2_RESPONSE_CODE:n | UI2 | Response code and status received from device. Read only. | 85.73:n |
HART.DEVICE_2_ACTIVE_ALARMS:n | UI1 | Active alarms reported by device. Read only. | 85.74:n |
HART.DEVICE_2_CURRENT:n | R4 | Current in milliamps. Read only. | 85.75:n |
HART.DEVICE_2_PERCENT_RANGE:n | R4 | Percent of range reported by device. Read only. | 85.76:n |
HART.DEVICE_2_FAILSAFE_ENABLE:n | UI1 | Enables the use of fail safe values for the dynamic variables when the unit resets. | 85.77:n |
HART.DEVICE_2_PV_UNITS:n | UI1 | Units code for primary variable reported by device. Read only. | 85.78:n |
HART.DEVICE_2_PV:n | R4 | Value of primary variable reported by device. Read only. | 85.79:n |
HART.DEVICE_2_PV_FAILSAFE:n | R4 | Primary fail safe value for device. | 85.80:n |
HART.DEVICE_2_SV_UNITS:n | UI1 | Units code for secondary variable reported by device. Read only. | 85.81:n |
HART.DEVICE_2_SV:n | R4 | Value of secondary variable reported by device. Read only. | 85.82:n |
HART.DEVICE_2_SV_FAILSAFE:n | R4 | Secondary fail safe value for device. | 85.83:n |
HART.DEVICE_2_TV_UNITS:n | UI1 | Units code for tertiary variable reported by device. Read only. | 85.84:n |
HART.DEVICE_2_TV:n | R4 | Value of tertiary variable reported by device. Read only. | 85.85:n |
HART.DEVICE_2_TV_FAILSAFE:n | R4 | Tertiary fail safe value for device. | 85.86:n |
HART.DEVICE_2_FV_UNITS:n | UI1 | Units code for fourth variable reported by device. Read only. | 85.87:n |
HART.DEVICE_2_FV:n | R4 | Value of fourth variable reported by device. Read only. | 85.88:n |
HART.DEVICE_2_FV_FAILSAFE:n | R4 | Fourth fail safe value for device. | 85.89:n |
HART.DEVICE_2_SLOT_0_ASSIGN:n | UI1 | Slot 0 variable to request from device. | 85.90:n |
HART.DEVICE_2_SLOT_0_UNITS:n | UI1 | Units of slot 0 variable to request from device. Read only. | 85.91:n |
HART.DEVICE_2_SLOT_0_VARIABLE:n | R4 | Value of slot 0 variable requested from device. | 85.92:n |
HART.DEVICE_2_SLOT_1_ASSIGN:n | UI1 | Slot 1 variable to request from device. | 85.93:n |
HART.DEVICE_2_SLOT_1_UNITS:n | UI1 | Units of slot 1 variable to request from device. Read only. | 85.94:n |
HART.DEVICE_2_SLOT_1_VARIABLE:n | R4 | Value of slot 1 variable requested from device. | 85.95:n |
HART.DEVICE_2_SLOT_2_ASSIGN:n | UI1 | Slot 2 variable to request from device. | 85.96:n |
HART.DEVICE_2_SLOT_2_UNITS:n | UI1 | Units of slot 2 variable to request from device. Read only. | 85.97:n |
HART.DEVICE_2_SLOT_2_VARIABLE:n | R4 | Value of slot 2 variable requested from device. | 85.98:n |
HART.DEVICE_2_SLOT_3_ASSIGN:n | UI1 | Slot 3 variable to request from device. | 85.99:n |
HART.DEVICE_2_SLOT_3_UNITS:n | UI1 | Units of slot 3 variable to request from device. Read only. | 85.100:n |
HART.DEVICE_2_SLOT_3_VARIABLE:n | R4 | Value of slot 3 variable requested from device. | 85.101:n |
HART.DEVICE_2_MESSAGE:n | STRING | 40 character device message. | 85.102:n |
HART.DEVICE_2_DESCRIPTION:n | STRING | 20 character device description. | 85.103:n |
HART.DEVICE_2_MANU_ID:n | UI2 | Device manufacture ID. Read only. | 85.104:n |
HART.DEVICE_2_SERIAL:n | UI4 | Device serial number. Read only. | 85.105:n |
HART.DEVICE_2_ID_NUMBER:n | UI4 | Device sensor units. Read only. | 85.105:n |
HART.DEVICE_2_SENSOR_UNITS:n | UI1 | Device sensor units. Read only. | 85.107:n |
HART.DEVICE_2_SENSOR_UPPER_LIM:n | R4 | Device sensor upper limit. Read only. | 85.108:n |
HART.DEVICE_2_SENSOR_LOWER_LIM:n | R4 | Device sensor lower limit. Read only. | 85.109:n |
HART.DEVICE_2_MINIMUM_SPAN:n | R4 | Device minimum sensor span. Read only. | 85.110:n |
HART.DEVICE_2_OUTPUT_UNITS:n | UI1 | Device output units. Read only. | 85.111:n |
HART.DEVICE_2_OUTPUT_UPPER_LIM:n | R4 | Device output upper limit. Read only. | 85.112:n |
HART.DEVICE_2_OUTPUT_LOWER_LIM:n | R4 | Device output lower limit. Read only. | 85.113:n |
HART.DEVICE_2_DAMPING_VALUE:n | R4 | Device damping value. Read only. | 85.114:n |
HART.DEVICE_3_POLL_MODE:n | UI1 | The polling mode for the device. 0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update. | 85.115:n |
HART.DEVICE_3_POLL_ADDRESS:n | UI1 | Polling address for the device. Read only. | 85.116:n |
HART.DEVICE_3_STATUS:n | UI1 | 0=no device found, 1=communication, 2=comm error. | 85.117:n |
HART.DEVICE_3_ACTUAL_SCAN_PERIOD:n | R4 | Period at which device is being updates. | 85.118:n |
HART. DEVICE_3_TAG:n | STRING | 10 character tag that resides in this device. Read only. | 85.119:n |
HART.DEVICE_3_RESPONSE_CODE:n | UI2 | Response code and status received from device. Read only. | 85.120:n |
HART.DEVICE_3_ACTIVE_ALARMS:n | UI1 | Active alarms reported by device. Read only. | 85.121:n |
HART.DEVICE_3_CURRENT:n | R4 | Current in milliamps. Read only. | 85.122:n |
HART.DEVICE_3_PERCENT_RANGE:n | R4 | Percent of range reported by device. Read only. | 85.123:n |
HART.DEVICE_3_FAILSAFE_ENABLE:n | UI1 | Enables the use of fail safe values for the dynamic variables when the unit resets. | 85.124:n |
HART.DEVICE_3_PV_UNITS:n | UI1 | Units code for primary variable reported by device. Read only. | 85.125:n |
HART.DEVICE_3_PV:n | R4 | Value of primary variable reported by device. Read only. | 85.126:n |
HART.DEVICE_3_PV_FAILSAFE:n | R4 | Primary fail safe value for device. | 85.127:n |
HART.DEVICE_3_SV_UNITS:n | UI1 | Units code for secondary variable reported by device. Read only. | 85.128:n |
HART.DEVICE_3_SV:n | R4 | Value of secondary variable reported by device. Read only. | 85.129:n |
HART.DEVICE_3_SV_FAILSAFE:n | R4 | Secondary fail safe value for device. | 85.130:n |
HART.DEVICE_3_TV_UNITS:n | UI1 | Units code for tertiary variable reported by device. Read only. | 85.131:n |
HART.DEVICE_3_TV:n | R4 | Value of tertiary variable reported by device. Read only. | 85.132:n |
HART.DEVICE_3_TV_FAILSAFE:n | R4 | Tertiary fail safe value for device. | 85.133:n |
HART.DEVICE_3_FV_UNITS:n | UI1 | Units code for fourth variable reported by device. Read only. | 85.134:n |
HART.DEVICE_3_FV:n | R4 | Value of fourth variable reported by device. Read only. | 85.135:n |
HART.DEVICE_3_FV_FAILSAFE:n | R4 | Fourth fail safe value for device. | 85.136:n |
HART.DEVICE_3_SLOT_0_ASSIGN:n | UI1 | Slot 0 variable to request from device. | 85.137:n |
HART.DEVICE_3_SLOT_0_UNITS:n | UI1 | Units of slot 0 variable to request from device. Read only. | 85.138:n |
HART.DEVICE_3_SLOT_0_VARIABLE:n | R4 | Value of slot 0 variable requested from device. | 85.139:n |
HART.DEVICE_3_SLOT_1_ASSIGN:n | UI1 | Slot 1 variable to request from device. | 85.140:n |
HART.DEVICE_3_SLOT_1_UNITS:n | UI1 | Units of slot 1 variable to request from device. Read only. | 85.141:n |
HART.DEVICE_3_SLOT_1_VARIABLE:n | R4 | Value of slot 1 variable requested from device. | 85.142:n |
HART.DEVICE_3_SLOT_2_ASSIGN:n | UI1 | Slot 2 variable to request from device. | 85.143:n |
HART.DEVICE_3_SLOT_2_UNITS:n | UI1 | Units of slot 2 variable to request from device. Read only. | 85.144:n |
HART.DEVICE_3_SLOT_2_VARIABLE:n | R4 | Value of slot 2 variable requested from device. | 85.145:n |
HART.DEVICE_3_SLOT_3_ASSIGN:n | UI1 | Slot 3 variable to request from device. | 85.146:n |
HART.DEVICE_3_SLOT_3_UNITS:n | UI1 | Units of slot 3 variable to request from device. Read only. | 85.147:n |
HART.DEVICE_3_SLOT_3_VARIABLE:n | R4 | Value of slot 3 variable requested from device. | 85.148:n |
HART.DEVICE_3_MESSAGE:n | STRING | 40 character device message. | 85.149:n |
HART.DEVICE_3_DESCRIPTION:n | STRING | 20 character device description. | 85.150:n |
HART.DEVICE_3_MANU_ID:n | UI2 | Device manufacture ID. Read only. | 85.151:n |
HART.DEVICE_3_SERIAL:n | UI4 | Device serial number. Read only. | 85.152:n |
HART.DEVICE_3_ID_NUMBER:n | UI4 | Device sensor units. Read only. | 85.153:n |
HART.DEVICE_3_SENSOR_UNITS:n | UI1 | Device sensor units. Read only. | 85.154:n |
HART.DEVICE_3_SENSOR_UPPER_LIM:n | R4 | Device sensor upper limit. Read only. | 85.155:n |
HART.DEVICE_3_SENSOR_LOWER_LIM:n | R4 | Device sensor lower limit. Read only. | 85.156:n |
HART.DEVICE_3_MINIMUM_SPAN:n | R4 | Device minimum sensor span. Read only. | 85.157:n |
HART.DEVICE_3_OUTPUT_UNITS:n | UI1 | Device output units. Read only. | 85.158:n |
HART.DEVICE_3_OUTPUT_UPPER_LIM:n | R4 | Device output upper limit. Read only. | 85.159:n |
HART.DEVICE_3_OUTPUT_LOWER_LIM:n | R4 | Device output lower limit. Read only. | 85.160:n |
HART.DEVICE_3_DAMPING_VALUE:n | R4 | Device damping value. Read only. | 85.161:n |
HART.DEVICE_4_POLL_MODE:n | UI1 | The polling mode for the device. 0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update. | 85.162:n |
HART.DEVICE_4_POLL_ADDRESS:n | UI1 | Polling address for the device. Read only. | 85.163:n |
HART.DEVICE_4_STATUS:n | UI1 | 0=no device found, 1=communication, 2=comm error. | 85.164:n |
HART.DEVICE_4_ACTUAL_SCAN_PERIOD:n | R4 | Period at which device is being updates. | 85.165:n |
HART. DEVICE_4_TAG:n | STRING | 10 character tag that resides in this device. Read only. | 85.166:n |
HART.DEVICE_4_RESPONSE_CODE:n | UI2 | Response code and status received from device. Read only. | 85.167:n |
HART.DEVICE_4_ACTIVE_ALARMS:n | UI1 | Active alarms reported by device. Read only. | 85.168:n |
HART.DEVICE_4_CURRENT:n | R4 | Current in milliamps. Read only. | 85.169:n |
HART.DEVICE_4_PERCENT_RANGE:n | R4 | Percent of range reported by device. Read only. | 85.170:n |
HART.DEVICE_4_FAILSAFE_ENABLE:n | UI1 | Enables the use of fail safe values for the dynamic variables when the unit resets. | 85.171:n |
HART.DEVICE_4_PV_UNITS:n | UI1 | Units code for primary variable reported by device. Read only. | 85.172:n |
HART.DEVICE_4_PV:n | R4 | Value of primary variable reported by device. Read only. | 85.173:n |
HART.DEVICE_4_PV_FAILSAFE:n | R4 | Primary fail safe value for device. | 85.174:n |
HART.DEVICE_4_SV_UNITS:n | UI1 | Units code for secondary variable reported by device. Read only. | 85.175:n |
HART.DEVICE_4_SV:n | R4 | Value of secondary variable reported by device. Read only. | 85.176:n |
HART.DEVICE_4_SV_FAILSAFE:n | R4 | Secondary fail safe value for device. | 85.177:n |
HART.DEVICE_4_TV_UNITS:n | UI1 | Units code for tertiary variable reported by device. Read only. | 85.178:n |
HART.DEVICE_4_TV:n | R4 | Value of tertiary variable reported by device. Read only. | 85.179:n |
HART.DEVICE_4_TV_FAILSAFE:n | R4 | Tertiary fail safe value for device. | 85.180:n |
HART.DEVICE_4_FV_UNITS:n | UI1 | Units code for fourth variable reported by device. Read only. | 85.181:n |
HART.DEVICE_4_FV:n | R4 | Value of fourth variable reported by device. Read only. | 85.182:n |
HART.DEVICE_4_FV_FAILSAFE:n | R4 | Fourth fail safe value for device. | 85.183:n |
HART.DEVICE_4_SLOT_0_ASSIGN:n | UI1 | Slot 0 variable to request from device. | 85.184:n |
HART.DEVICE_4_SLOT_0_UNITS:n | UI1 | Units of slot 0 variable to request from device. Read only. | 85.185:n |
HART.DEVICE_4_SLOT_0_VARIABLE:n | R4 | Value of slot 0 variable requested from device. | 85.186:n |
HART.DEVICE_4_SLOT_1_ASSIGN:n | UI1 | Slot 1 variable to request from device. | 85.187:n |
HART.DEVICE_4_SLOT_1_UNITS:n | UI1 | Units of slot 1 variable to request from device. Read only. | 85.188:n |
HART.DEVICE_4_SLOT_1_VARIABLE:n | R4 | Value of slot 1 variable requested from device. | 85.189:n |
HART.DEVICE_4_SLOT_2_ASSIGN:n | UI1 | Slot 2 variable to request from device. | 85.190:n |
HART.DEVICE_4_SLOT_2_UNITS:n | UI1 | Units of slot 2 variable to request from device. Read only. | 85.191:n |
HART.DEVICE_4_SLOT_2_VARIABLE:n | R4 | Value of slot 2 variable requested from device. | 85.192:n |
HART.DEVICE_4_SLOT_3_ASSIGN:n | UI1 | Slot 3 variable to request from device. | 85.193:n |
HART.DEVICE_4_SLOT_3_UNITS:n | UI1 | Units of slot 3 variable to request from device. Read only. | 85.194:n |
HART.DEVICE_4_SLOT_3_VARIABLE:n | R4 | Value of slot 3 variable requested from device. | 85.195:n |
HART.DEVICE_4_MESSAGE:n | STRING | 40 character device message. | 85.196:n |
HART.DEVICE_4_DESCRIPTION:n | STRING | 20 character device description. | 85.197:n |
HART.DEVICE_4_MANU_ID:n | UI2 | Device manufacture ID. Read only. | 85.198:n |
HART.DEVICE_4_SERIAL:n | UI4 | Device serial number. Read only. | 85.199:n |
HART.DEVICE_4_ID_NUMBER:n | UI4 | Device sensor units. Read only. | 85.200:n |
HART.DEVICE_4_SENSOR_UNITS:n | UI1 | Device sensor units. Read only. | 85.201:n |
HART.DEVICE_4_SENSOR_UPPER_LIM:n | R4 | Device sensor upper limit. Read only. | 85.202:n |
HART.DEVICE_4_SENSOR_LOWER_LIM:n | R4 | Device sensor lower limit. Read only. | 85.203:n |
HART.DEVICE_4_MINIMUM_SPAN:n | R4 | Device minimum sensor span. Read only. | 85.204:n |
HART.DEVICE_4_OUTPUT_UNITS:n | UI1 | Device output units. Read only. | 85.205:n |
HART.DEVICE_4_OUTPUT_UPPER_LIM:n | R4 | Device output upper limit. Read only. | 85.206:n |
HART.DEVICE_4_OUTPUT_LOWER_LIM:n | R4 | Device output lower limit. Read only. | 85.207:n |
HART.DEVICE_4_DAMPING_VALUE:n | R4 | Device damping value. Read only. | 85.208:n |
HART.DEVICE_5_POLL_MODE:n | UI1 | The polling mode for the device. 0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update. | 85.209:n |
HART.DEVICE_5_POLL_ADDRESS:n | UI1 | Polling address for the device. Read only. | 85.210:n |
HART.DEVICE_5_STATUS:n | UI1 | 0=no device found, 1=communication, 2=comm error. | 85.211:n |
HART.DEVICE_5_ACTUAL_SCAN_PERIOD:n | R4 | Period at which device is being updates. | 85.212:n |
HART. DEVICE_5_TAG:n | STRING | 10 character tag that resides in this device. Read only. | 85.213:n |
HART.DEVICE_5_RESPONSE_CODE:n | UI2 | Response code and status received from device. Read only. | 85.214:n |
HART.DEVICE_5_ACTIVE_ALARMS:n | UI1 | Active alarms reported by device. Read only. | 85.215:n |
HART.DEVICE_5_CURRENT:n | R4 | Current in milliamps. Read only. | 85.216:n |
HART.DEVICE_5_PERCENT_RANGE:n | R4 | Percent of range reported by device. Read only. | 85.217:n |
HART.DEVICE_5_FAILSAFE_ENABLE:n | UI1 | Enables the use of fail safe values for the dynamic variables when the unit resets. | 85.218:n |
HART.DEVICE_5_PV_UNITS:n | UI1 | Units code for primary variable reported by device. Read only. | 85.219:n |
HART.DEVICE_5_PV:n | R4 | Value of primary variable reported by device. Read only. | 85.220:n |
HART.DEVICE_5_PV_FAILSAFE:n | R4 | Primary fail safe value for device. | 85.221:n |
HART.DEVICE_5_SV_UNITS:n | UI1 | Units code for secondary variable reported by device. Read only. | 85.222:n |
HART.DEVICE_5_SV:n | R4 | Value of secondary variable reported by device. Read only. | 85.223:n |
HART.DEVICE_5_SV_FAILSAFE:n | R4 | Secondary fail safe value for device. | 85.224:n |
HART.DEVICE_5_TV_UNITS:n | UI1 | Units code for tertiary variable reported by device. Read only. | 85.225:n |
HART.DEVICE_5_TV:n | R4 | Value of tertiary variable reported by device. Read only. | 85.226:n |
HART.DEVICE_5_TV_FAILSAFE:n | R4 | Tertiary fail safe value for device. | 85.227:n |
HART.DEVICE_5_FV_UNITS:n | UI1 | Units code for fourth variable reported by device. Read only. | 85.228:n |
HART.DEVICE_5_FV:n | R4 | Value of fourth variable reported by device. Read only. | 85.229:n |
HART.DEVICE_5_FV_FAILSAFE:n | R4 | Fourth fail safe value for device. | 85.230:n |
HART.DEVICE_5_SLOT_0_ASSIGN:n | UI1 | Slot 0 variable to request from device. | 85.231:n |
HART.DEVICE_5_SLOT_0_UNITS:n | UI1 | Units of slot 0 variable to request from device. Read only. | 85.232:n |
HART.DEVICE_5_SLOT_0_VARIABLE:n | R4 | Value of slot 0 variable requested from device. | 85.233:n |
HART.DEVICE_5_SLOT_1_ASSIGN:n | UI1 | Slot 1 variable to request from device. | 85.234:n |
HART.DEVICE_5_SLOT_1_UNITS:n | UI1 | Units of slot 1 variable to request from device. Read only. | 85.235:n |
HART.DEVICE_5_SLOT_1_VARIABLE:n | R4 | Value of slot 1 variable requested from device. | 85.236:n |
HART.DEVICE_5_SLOT_2_ASSIGN:n | UI1 | Slot 2 variable to request from device. | 85.237:n |
HART.DEVICE_5_SLOT_2_UNITS:n | UI1 | Units of slot 2 variable to request from device. Read only. | 85.238:n |
HART.DEVICE_5_SLOT_2_VARIABLE:n | R4 | Value of slot 2 variable requested from device. | 85.239:n |
HART.DEVICE_5_SLOT_3_ASSIGN:n | UI1 | Slot 3 variable to request from device. | 85.240:n |
HART.DEVICE_5_SLOT_3_UNITS:n | UI1 | Units of slot 3 variable to request from device. Read only. | 85.241:n |
HART.DEVICE_5_SLOT_3_VARIABLE:n | R4 | Value of slot 3 variable requested from device. | 85.242:n |
HART.DEVICE_5_MESSAGE:n | STRING | 40 character device message. | 85.243:n |
HART.DEVICE_5_DESCRIPTION:n | STRING | 20 character device description. | 85.244:n |
HART.DEVICE_5_MANU_ID:n | UI2 | Device manufacture ID. Read only. | 85.245:n |
HART.DEVICE_5_SERIAL:n | UI4 | Device serial number. Read only. | 85.246:n |
HART.DEVICE_5_ID_NUMBER:n | UI4 | Device sensor units. Read only. | 85.247:n |
HART.DEVICE_5_SENSOR_UNITS:n | UI1 | Device sensor units. Read only. | 85.248:n |
HART.DEVICE_5_SENSOR_UPPER_LIM:n | R4 | Device sensor upper limit. Read only. | 85.249:n |
HART.DEVICE_5_SENSOR_LOWER_LIM:n | R4 | Device sensor lower limit. Read only. | 85.250:n |
HART.DEVICE_5_MINIMUM_SPAN:n | R4 | Device minimum sensor span. Read only. | 85.251:n |
HART.DEVICE_5_OUTPUT_UNITS:n | UI1 | Device output units. Read only. | 85.252:n |
HART.DEVICE_5_OUTPUT_UPPER_LIM:n | R4 | Device output upper limit. Read only. | 85.253:n |
HART.DEVICE_5_OUTPUT_LOWER_LIM:n | R4 | Device output lower limit. Read only. | 85.254:n |
HART.DEVICE_5_DAMPING_VALUE:n | R4 | Device damping value. Read only. | 85.255:n |
Point Type 91 - System Items
Item | Data Type | Description | T.P:L |
---|---|---|---|
SYSTEM.ROC_UNIT or SYSTEM.ROC_ADDRESS | UINT8 | One-byte unit code of the station address. The unit code for a ROC address is configurable by the user. A 0 is used for broadcast. | 91.0:n |
SYSTEM.ROC_GROUP | UINT8 | Group code of the station address. | 91.1:n |
SYSTEM.STATION_NAME | AC | A 20-character ASCII field for the station name. | 91.2:n |
SYSTEM.PART_VERSION | AC | Contains the software part number and version number string. READ ONLY. | 91.3:n |
SYSTEM.TIME_CREATED | AC | Contains the time and date stamp the firmware was created. READ ONLY. | 91.4:n |
SYSTEM.MANU_ID | AC | Contains manufacturing identification string. READ ONLY. | 91.5:n |
SYSTEM.PROD_DESCRIPTION | AC | Contains manufacturing description of product. READ ONLY. | 91.6:n |
SYSTEM.SERIAL_NUMBER | UINT32 | Contains the serial number for the unit. READ ONLY. | 91.7:n |
SYSTEM.MAX_EVENTS or SYSTEM.ROM_EVENTS | UINT16 | Contains the maximum number of events that the Event Log may contain. READ ONLY. | 91.8:n |
SYSTEM.MAX_ALARMS or SYSTEM.ROM_ALARMS | UINT16 | Contains the maximum number of alarms that the Alarm Log may contain. READ ONLY. | 91.9:n |
SYSTEM.MAX_PIDS or SYSTEM.ROM_PIDS | UINT8 | Contains the maximum number of PID loops that may run on the system. READ ONLY. | 91.10:n |
SYSTEM.MAX_AGAS or SYSTEM.ROM_AGAS | UINT8 | Contains the maximum number of Meter Runs that may run on the system. READ ONLY. | 91.11:n |
SYSTEM.MAX_FST or SYSTEM.ROM_FST | UINT8 | Contains the maximum number of FSTs that may run on the system. READ ONLY. | 91.12:n |
SYSTEM.EVENT_INDEX | UINT16 | Indicates the current event index in the Event Log. READ ONLY. | 91.13:n |
SYSTEM.ALARM_INDEX | UINT16 | Indicates the current alarm index in the Alarm Log. READ ONLY. | 91.14:n |
SYSTEM.ACTIVE_PIDS | UINT8 | Number of active PIDs | 91.15:n |
SYSTEM.ACTIVE_STATIONS | UINT8 | Number of active stations. | 91.16:n |
SYSTEM.ACTIVE_ORIFICE | UINT8 | Number of active orifice meter runs. | 91.17:n |
SYSTEM.ACTIVE_TURBINE | UINT8 | Number of active turbine meter runs. | 91.18:n |
SYSTEM.FST_CLEAR | UINT8 | Setting this parameter clears FST code from Flash ROM. • 0 – Does nothing. • 1 – Initiates clearing of FST code. | 91.19:n |
SYSTEM.CLEAR_CONFIG | UINT8 | Used to clear the internal configuration memory stored in flash ROM. • 0 = Do nothing • 1 = Enable clearing of Configuration Memory | 91.20:n |
SYSTEM.WRITE_CONFIG | UINT8 | Used to command the ROC to store certain point types (indicated throughout this document) to flash configuration memory • 0 = Do nothing • 1 = Perform Write to Configuration Memory | 91.21:n |
SYSTEM.WRITE_COMPLETE | UINT8 | Used to indicate that the system is the process of writing the configuration to flash ROM • 0 = Currently Performing the Write • 1 = Completed the Write READ ONLY. | 91.22:n |
SYSTEM.MPU_LOADING | FLP | Contains the current percentage of time the CPU is being loaded, updated every 5 seconds. READ ONLY. | 91.23:n |
SYSTEM.RESERVED | UINT8 | Unused parameter. READ ONLY. | 91.24:n |
SYSTEM.IO_SCANNING | UINT8 | Used to enable or disable scanning of all I/O in the system. • 0 = Disabled • 1 = Enabled | 91.25:n |
SYSTEM.WARM_START | UINT8 | Used to re-start the system. A warm start is a reboot of the system without performing all the power-on-self tests. • 0 = Do nothing • 1 = Perform Warm Start | 91.26:n |
SYSTEM.COLD_START | UINT8 | Used to re-start the system. A cold start always includes starting from the boot sector and performing power-on-self tests, plus the following options. • 0 = Do nothing • 1 = Restore Configuration from Flash • 2 = Clear Alarms • 3 = Clear Events • 4 = Clear FSTs • 5 = Clear History & Meter Runs • 6 = Restore Configuration from Flash, Clear Alarms/Events/FST’s/History/Meter Runs • 7 = Restore Configuration from Defaults | 91.27:n |
SYSTEM.LCD_INSTALLED | UINT8 | • 0 = No LCD installed or LCD is disabled • 1 = LCD installed and enabled READ ONLY. | 91.28:n |
SYSTEM.LCD_POWERSAVE | UINT8 | Enables or disables the power saving feature of the LCD. When enabled the display will stay on until the power off time expires. 0 – Disable Power Saving, 1 – Enable Power Saving. Note: Since this functionality has not yet be added to the firmware (as of Version 1.00) this parameter is currently R/O. When the functionality is added, it will be made R/W. | 91.29:n |
SYSTEM.LCD_OWNER | UINT8 | The current owner of the LCD. This is used if a user C program is needed to run the LCD. • 0 = LCD • 1 = User C Program 1 • 2 = User C Program 2 • 3 = User C Program 3 • 4 = User C Program 4 • 5 = User C Program 5 • 6 = User C Program 6 • 7 = User C Program 7 • 8 = User C Program 8 | 91.30:n |
SYSTEM.BAUD_RATE_0 | UINT32 | The baud rate that baud rate generator #0 is to be set to. | 91.31:n |
SYSTEM.BAUD_RATE_1 | UINT32 | The baud rate that baud rate generator #1 is to be set to. | 91.32:n |
SYSTEM.BAUD_RATE_2 | UINT32 | The baud rate that baud rate generator #2 is to be set to. | 91.33:n |
SYSTEM.BAUD_RATE_3 | UINT32 | The baud rate that baud rate generator #3 is to be set to. | 91.34:n |
SYSTEM.CRC_CHECK | UINT8 | The CRC check flag. If this flag is enabled, a CRC will be appended to all messages and a CRC will be expected on all received messages. Disabled = 0, Enabled = 1. | 91.35:n |
SYSTEM.LED_ENABLE | UINT8 | Indicates the number of minutes the LEDs will be on before automatically turning themselves off. (The LED buttons will active the LEDs for the configured time). • 0 = LEDs always on • 1 - 60 = Number of minutes LEDs will be on | 91.36:n |
SYSTEM.BOOT_PART_NUM | AC | Contains the boot software part number and version number string. READ ONLY. | 91.37:n |
SYSTEM.BOOT_FIRMWARE_TIME | AC | Contains the time and date stamp the boot firmware was created. READ ONLY. | 91.38:n |
SYSTEM.ACTIVE_ODORIZERS | UINT8 | Number of active odorizers | 91.39:n |
SYSTEM.CLEAR_HISTORY_CONFIG |
| Clears history database and resets configuration back to factory defaults without power cycling the ROC. Don't clear = 0, Clear = 1. | 91.40:n |
...
Item | Data Type | Description | T.P:L |
---|---|---|---|
DO.POINT_TAG_ID | AC | Identification name for specific AO. Values must be printable ASCII characters. | 102.0:n |
DO.UNITS_TAG | AC | Describes the units used by the AO. Values must be printable ASCII characters. | 102.1:n |
DO.SCANNING | UINT8 | If disabled, no changes to the output will occur. If in Manual, only the user can change the values of the AO. If in automatic, anything can change the values of the AO. • 0 = Disabled • 1 = Automatic • 2 = Manual | 102.2:n |
DO.ALARMING | UINT8 | If enabled, alarms may be generated and sent to the Alarm Log. • 0 = Disabled • 1 = Enabled | 102.3:n |
DO.SRBX_ON_CLEAR | UINT8 | Indicates a SRBX alarm is desired if an alarm condition clears • 0 = SRBX on Clear Disabled • 1 = SRBX on Clear Enabled. | 102.4:n |
DO.SRBX_ON_SET | UINT8 | Indicates a SRBX alarm is desired if an alarm condition occurs. • 0 = SRBX on Set Disabled • 1 = SRBX on Set Enabled | 102.5:n |
DO.ALARM_CODE | BIN | If bit 5 is set, the Scanning (parameter #2) has been set to Manual. If clear, the Scanning (parameter #2) has been set to either Disable or Automatic If bit 7 is set, the Scanning (parameter #2) has been disabled. If clear, the Scanning (parameter #2) has been set to either Automatic or Manual. READ ONLY. | 102.6:n |
DO.FAILSAFE_ON_RESET | UINT8 | If enabled, the Status (parameter #8) will be set to the status indicated in ‘Failsafe Status Value’ (Parameter #22) on a restart of any kind. If disabled, the last Status before the restart will be used. 0 = Output Last Status on Reset, 1 = Use Failsafe value on Reset. | 102.7:n |
DO.STATUS | UINT8 | Indicates what state the DO is currently in, ON (1) or OFF (0). | 102.8:n |
DO.ACCUM_VALUE | UINT32 | Number of times the Status (parameter #8) goes from OFF to ON. | 102.9:n |
DO.MOMENTARY_MODE | UINT8 | If enabled, the Status (parameter #8) will be turned ON for the entered Time On (parameter #14) and then be turned OFF. • 0 = Momentary Disabled • 1 = Momentary Enabled | 102.10:n |
DO.MOMENTARY_ACTIVE | UINT8 | Indicates that the DO currently has the Momentary ability active. • 0 = Momentary Not Active • 1 = Momentary Active | 102.11:n |
DO.TOGGLE_MODE | UINT8 | If enabled, the Status (parameter #8) will be turned ON for the entered Time On (parameter #14) and then turned OFF for the same Time On. The Status will continue to cycle between the ON and OFF states. • 0 = Toggle Disabled • 1 = Toggle Enabled | 102.12:n |
DO.TDO_MODE | UINT8 | If enabled, the Status (parameter #8) will be turned ON for a calculated Time On (parameter #14) based upon the entered EU Value (parameter #20). After the Time On has expired, the Status will be turned OFF and remain that way until a new EU Value is entered. • 0 = TDO Disabled • 1 = TDO Enabled | 102.13:n |
DO.TIME_ON | FLP | Number of seconds the Status (parameter #8) will be turned ON for if in TDO, Toggle, or Momentary Mode. | 102.14:n |
DO.CYCLE_TIME | FLP | Number of seconds for when TDO Mode (parameter #13) and Toggle Mode (parameter #12) are selected. The Status (parameter #8) will be ON for the calculated Time On (parameter #14) based upon the entered EU Value (parameter #20). The Status will then be turned OFF based upon the Cycle Time minus the Time On. | 102.15:n |
DO.LOW_READING_TIME | FLP | Minimum number of seconds the calculated Time On (parameter #14) will be when the entered EU Value (parameter #20) is less than or equal to the entered Low Reading EU (parameter #18). | 102.16:n |
DO.HIGH_READING_TIME | FLP | Maximum number of seconds the calculated Time On (parameter #14) will be when they entered EU Value (parameter #20) is greater than or equal to the entered High Reading EU (parameter #19). | 102.17:n |
DO.LOW_READING_EU | FLP | Minimum EU Value (parameter #20) possible. | 102.18:n |
DO.HIGH_READING_EU | FLP | Maximum EU Value (parameter #20) possible. | 102.19:n |
DO.EU_VALUE | FLP | Value in Engineering Units. | 102.20:n |
DO.MANUAL_VALUE | UINT8 | Manual Value used when Scanning (parameter #2) is in manual mode | 102.21:n |
DO.FAILSAFE_STATUS | UINT8 | This is the status the output will be placed in when the unit is started and the Failsafe on Reset Parameter (Parameter 7) is set to 1, Use Failsafe value on reset. | 102.22:n |
DO.RESERVED | FLP | Max Scan Period READ ONLY. | 102.23:n |
DO.PHYSICAL_OUTPUT | UINT8 | Indicates the DO’s current state. Valid values are 0 (OFF) and 1 (ON). | 102.24:n |
Point Type 103 - ROC 800 Analog Input Items
...
Item | Data Type | Description |
---|---|---|
GCWrite/Txn | Variant Array | Used for automated gas quality download. |
LastAlarmRecord/n | Date | Timestamp of the last alarm record retrieved from meter number 'n'. |
LastDailyRecord/n | Date | Timestamp of the last daily record retrieved from meter number 'n'. |
LastEventRecord/n | Date | Timestamp of the last event record retrieved from meter number 'n'. |
LastHourlyRecord/n | Date | Timestamp of the last hourly record retrieved from meter number 'n'. |
ClockSet | Date | Set the Date and Time on the device. |
LastTimeSync | Date | Timestamp of the last time synchronization attempt. |
LastTimeSyncResult | I4 | Result of the last time synchronization attempt. |
MoveDaily | I2 | Move the daily history retrieval pointer for meter run 1. Write a positive number to move the pointer back in time, a negative number to move the pointer forward in time. The written value represents the number of days to move. |
MoveHourly | I2 | Move the hourly history retrieval pointer for meter run 1. Write a positive number to move the pointer back in time, a negative number to move the pointer forward in time. The written value represents the number of hours to move. |
Reinitialize | I2 | Re-read the ROC configuration |
ResetAlarm | BOOL | Erase the Alarm history retrieval pointer for meter 1 all meters (and recollect all Alarm history during the next retrieval). |
ResetDaily | BOOL | Erase the daily history retrieval pointer for meter 1 all meters (and recollect all daily history during the next retrieval). |
ResetEvent | BOOL | Erase the event history retrieval pointer for meter 1 all meters (and recollect all event history during the next retrieval). |
ResetHourly | BOOL | Erase the hourly history retrieval pointer for meter 1 all meters (and recollect all hourly history during the next retrieval). |
RetrieveHistory | I2 | Retrieve enabled history. |
RetrieveMeterConfiguration | I2 | Retrieve enabled Meter Configuration. |
SkipDaily | I2 | Skip enabled history |
SkipHourly | I2 | Skip enabled history |
TimeSync | I2 | Perform time synchronization. |
...