Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

ItemData TypeDescriptionT.P:L

HART.CHANNEL_VERSION:n

STRING

10 character version number for the firmware in this channel. Read only.

85.0:n

HART.CHANNEL_IO:n

UI1

Indicates if channel is input (0) or output (1). Read only.

85.1:n

HART.COMM_MODE:n

UI1

0=Disabled, 1=Point to Point, 2=Multidrop.

85.2:n

HART.NUMBER_DEVICES:n

UI1

Number of devices connected in multidrop mode.

85.3:n

HART.COMM_STATUS:n

UI1

Communication status.  0=Not scanning, 1=Scanning normal, 2=Dual Master detected, 3=Pass thru, 4=Device in burst mode. Read only.

85.4:n

HART.ANALOG_MODE:n

UI1

Analog mode.  0=Disabled, 1=Enabled.

85.5:n

HART.PASS_THRU:n

UI1

Enables ROC protocol pass thru communication.  0=Disabled, 1=Enabled.

85.6:n

HART.PASS_THRU_TIMEOUT:n

UI4

Timeout (in millisecons) to resume after pass thru communications.

85.7:n

HART.HART_EU_VALUE:n

R4

EU value of analog input or output. Read only.

85.8:n

HART.HART_FAILSAFE_ON_RESET:n

UI1

0=Use last EU value on reset, 1=Use failsafe value on reset.

85.9:n

HART.HART_FAILSAFE_VALUE:n

R4

The value outputted when the unit is started.

85.10:n

HART.HART_MANUAL_VALUE:n

R4

The value used in output when scanning is in manual mode.

85.11:n

HART.HART_AUTO_VALUE:n

R4

The value used in output when scanning is in auto mode.

85.12:n

HART.HART_PHYSICAL_VALUE:n

R4

The current value of the output in engineering units.

85.13:n

HART.PHYSICAL_RAW_DA:n

UI2

Calculated digital-to-analog value.

85.14:n

HART.CALIBRATION_LIVE:n

R4

The live value when calibrating an AI

85.15:n

HART.CALIBRATION_ZERO:n

R4

The zero EU calibration value

85.16:n

HART.CALIBRATION_SPAN:n

R4

The span EU calibration value

85.17:n

HART.EU_RAW_VALUE:n

UI2

The EU value of AI or AO.

85.18:n

HART.EU_RAW_CALIBRATION_ZERO:n

UI2

The zero raw calibration value.

85.19:n

HART.EU_RAW_CALIBRATION_SPAN:n

UI2

The span raw calibration value.

85.20:n

HART.DEVICE_1_POLL_MODE:n

UI1

The polling mode for the device.  0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update.

85.21:n

HART.DEVICE_1_POLL_ADDRESS:n

UI1

Polling address for the device. Read only.

85.22:n

HART.DEVICE_1_STATUS:n

UI1

0=no device found, 1=communication, 2=comm error.

85.23:n

HART.DEVICE_1_ACTUAL_SCAN_PERIOD:n

R4

Period at which device is being updates.

85.24:n

HART. DEVICE_1_TAG:n

STRING

10 character tag that resides in this device. Read only.

85.25:n

HART.DEVICE_1_RESPONSE_CODE:n

UI2

Response code and status received from device. Read only.

85.26:n

HART.DEVICE_1_ACTIVE_ALARMS:n

UI1

Active alarms reported by device. Read only.

85.27:n

HART.DEVICE_1_CURRENT:n

R4

Current in milliamps. Read only.

85.28:n

HART.DEVICE_1_PERCENT_RANGE:n

R4

Percent of range reported by device. Read only.

85.29:n

HART.DEVICE_1_FAILSAFE_ENABLE:n

UI1

Enables the use of fail safe values for the dynamic variables when the unit resets. 

85.30:n

HART.DEVICE_1_PV_UNITS:n

UI1

Units code for primary variable reported by device. Read only.

85.31:n

HART.DEVICE_1_PV:n

R4

Value of primary variable reported by device. Read only.

85.32:n

HART.DEVICE_1_PV_FAILSAFE:n

R4

Primary fail safe value for device.

85.33:n

HART.DEVICE_1_SV_UNITS:n

UI1

Units code for secondary variable reported by device. Read only.

85.34:n

HART.DEVICE_1_SV:n

R4

Value of secondary variable reported by device. Read only.

85.35:n

HART.DEVICE_1_SV_FAILSAFE:n

R4

Secondary fail safe value for device.

85.36:n

HART.DEVICE_1_TV_UNITS:n

UI1

Units code for tertiary variable reported by device. Read only.

85.37:n

HART.DEVICE_1_TV:n

R4

Value of tertiary variable reported by device. Read only.

85.38:n

HART.DEVICE_1_TV_FAILSAFE:n

R4

Tertiary fail safe value for device.

85.39:n

HART.DEVICE_1_FV_UNITS:n

UI1

Units code for fourth variable reported by device. Read only. 

85.40:n

HART.DEVICE_1_FV:n

R4

Value of fourth variable reported by device. Read only.

85.41:n

HART.DEVICE_1_FV_FAILSAFE:n

R4

Fourth fail safe value for device.

85.42:n

HART.DEVICE_1_SLOT_0_ASSIGN:n

UI1

Slot 0 variable to request from device.

85.43:n

HART.DEVICE_1_SLOT_0_UNITS:n

UI1

Units of slot 0 variable to request from device. Read only.

85.44:n

HART.DEVICE_1_SLOT_0_VARIABLE:n

R4

Value of slot 0 variable requested from device.

85.45:n

HART.DEVICE_1_SLOT_1_ASSIGN:n

UI1

Slot 1 variable to request from device.

85.46:n

HART.DEVICE_1_SLOT_1_UNITS:n

UI1

Units of slot 1 variable to request from device. Read only.

85.47:n

HART.DEVICE_1_SLOT_1_VARIABLE:n

R4

Value of slot 1 variable requested from device.

85.48:n

HART.DEVICE_1_SLOT_2_ASSIGN:n

UI1

Slot 2 variable to request from device.

85.49:n

HART.DEVICE_1_SLOT_2_UNITS:n

UI1

Units of slot 2 variable to request from device. Read only.

85.50:n

HART.DEVICE_1_SLOT_2_VARIABLE:n

R4

Value of slot 2 variable requested from device.

85.51:n

HART.DEVICE_1_SLOT_3_ASSIGN:n

UI1

Slot 3 variable to request from device.

85.52:n

HART.DEVICE_1_SLOT_3_UNITS:n

UI1

Units of slot 3 variable to request from device. Read only.

85.53:n

HART.DEVICE_1_SLOT_3_VARIABLE:n

R4

Value of slot 3 variable requested from device.

85.54:n

HART.DEVICE_1_MESSAGE:n

STRING

40 character device message. 

85.55:n

HART.DEVICE_1_DESCRIPTION:n

STRING

20 character device description. 

85.56:n

HART.DEVICE_1_MANU_ID:n

UI2

Device manufacture ID. Read only.

85.57:n

HART.DEVICE_1_SERIAL:n

UI4

Device serial number. Read only.

85.58:n

HART.DEVICE_1_ID_NUMBER:n

UI4

Device sensor units. Read only.

85.59:n

HART.DEVICE_1_SENSOR_UNITS:n

UI1

Device sensor units. Read only.

85.60:n

HART.DEVICE_1_SENSOR_UPPER_LIM:n

R4

Device sensor upper limit. Read only.

85.61:n

HART.DEVICE_1_SENSOR_LOWER_LIM:n

R4

Device sensor lower limit. Read only.

85.62:n

HART.DEVICE_1_MINIMUM_SPAN:n

R4

Device minimum sensor span. Read only.

85.63:n

HART.DEVICE_1_OUTPUT_UNITS:n

UI1

Device output units. Read only.

85.64:n

HART.DEVICE_1_OUTPUT_UPPER_LIM:n

R4

Device output upper limit. Read only.

85.65:n

HART.DEVICE_1_OUTPUT_LOWER_LIM:n

R4

Device output lower limit. Read only.

85.66:n

HART.DEVICE_1_DAMPING_VALUE:n

R4

Device damping value. Read only.

85.67:n

HART.DEVICE_2_POLL_MODE:n

UI1

The polling mode for the device.  0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update.

85.68:n

HART.DEVICE_2_POLL_ADDRESS:n

UI1

Polling address for the device. Read only.

85.69:n

HART.DEVICE_2_STATUS:n

UI1

0=no device found, 1=communication, 2=comm error.

85.70:n

HART.DEVICE_2_ACTUAL_SCAN_PERIOD:n

R4

Period at which device is being updates.

85.71:n

HART. DEVICE_2_TAG:n

STRING

10 character tag that resides in this device. Read only. 

85.72:n

HART.DEVICE_2_RESPONSE_CODE:n

UI2

Response code and status received from device. Read only.

85.73:n

HART.DEVICE_2_ACTIVE_ALARMS:n

UI1

Active alarms reported by device. Read only.

85.74:n

HART.DEVICE_2_CURRENT:n

R4

Current in milliamps. Read only.

85.75:n

HART.DEVICE_2_PERCENT_RANGE:n

R4

Percent of range reported by device. Read only.

85.76:n

HART.DEVICE_2_FAILSAFE_ENABLE:n

UI1

Enables the use of fail safe values for the dynamic variables when the unit resets.

85.77:n

HART.DEVICE_2_PV_UNITS:n

UI1

Units code for primary variable reported by device. Read only.

85.78:n

HART.DEVICE_2_PV:n

R4

Value of primary variable reported by device. Read only.

85.79:n

HART.DEVICE_2_PV_FAILSAFE:n

R4

Primary fail safe value for device.

85.80:n

HART.DEVICE_2_SV_UNITS:n

UI1

Units code for secondary variable reported by device. Read only.

85.81:n

HART.DEVICE_2_SV:n

R4

Value of secondary variable reported by device. Read only.

85.82:n

HART.DEVICE_2_SV_FAILSAFE:n

R4

Secondary fail safe value for device.

85.83:n

HART.DEVICE_2_TV_UNITS:n

UI1

Units code for tertiary variable reported by device. Read only.

85.84:n

HART.DEVICE_2_TV:n

R4

Value of tertiary variable reported by device. Read only.

85.85:n

HART.DEVICE_2_TV_FAILSAFE:n

R4

Tertiary fail safe value for device.

85.86:n

HART.DEVICE_2_FV_UNITS:n

UI1

Units code for fourth variable reported by device. Read only.

85.87:n

HART.DEVICE_2_FV:n

R4

Value of fourth variable reported by device. Read only.

85.88:n

HART.DEVICE_2_FV_FAILSAFE:n

R4

Fourth fail safe value for device.

85.89:n

HART.DEVICE_2_SLOT_0_ASSIGN:n

UI1

Slot 0 variable to request from device.

85.90:n

HART.DEVICE_2_SLOT_0_UNITS:n

UI1

Units of slot 0 variable to request from device. Read only.

85.91:n

HART.DEVICE_2_SLOT_0_VARIABLE:n

R4

Value of slot 0 variable requested from device.

85.92:n

HART.DEVICE_2_SLOT_1_ASSIGN:n

UI1

Slot 1 variable to request from device.

85.93:n

HART.DEVICE_2_SLOT_1_UNITS:n

UI1

Units of slot 1 variable to request from device. Read only.

85.94:n

HART.DEVICE_2_SLOT_1_VARIABLE:n

R4

Value of slot 1 variable requested from device.

85.95:n

HART.DEVICE_2_SLOT_2_ASSIGN:n

UI1

Slot 2 variable to request from device.

85.96:n

HART.DEVICE_2_SLOT_2_UNITS:n

UI1

Units of slot 2 variable to request from device. Read only.

85.97:n

HART.DEVICE_2_SLOT_2_VARIABLE:n

R4

Value of slot 2 variable requested from device.

85.98:n

HART.DEVICE_2_SLOT_3_ASSIGN:n

UI1

Slot 3 variable to request from device.

85.99:n

HART.DEVICE_2_SLOT_3_UNITS:n

UI1

Units of slot 3 variable to request from device. Read only.

85.100:n

HART.DEVICE_2_SLOT_3_VARIABLE:n

R4

Value of slot 3 variable requested from device.

85.101:n

HART.DEVICE_2_MESSAGE:n

STRING

40 character device message. 

85.102:n

HART.DEVICE_2_DESCRIPTION:n

STRING

20 character device description. 

85.103:n

HART.DEVICE_2_MANU_ID:n

UI2

Device manufacture ID. Read only.

85.104:n

HART.DEVICE_2_SERIAL:n

UI4

Device serial number. Read only.

85.105:n

HART.DEVICE_2_ID_NUMBER:n

UI4

Device sensor units. Read only.

85.105:n

HART.DEVICE_2_SENSOR_UNITS:n

UI1

Device sensor units. Read only.

85.107:n

HART.DEVICE_2_SENSOR_UPPER_LIM:n

R4

Device sensor upper limit. Read only.

85.108:n

HART.DEVICE_2_SENSOR_LOWER_LIM:n

R4

Device sensor lower limit. Read only.

85.109:n

HART.DEVICE_2_MINIMUM_SPAN:n

R4

Device minimum sensor span. Read only.

85.110:n

HART.DEVICE_2_OUTPUT_UNITS:n

UI1

Device output units. Read only.

85.111:n

HART.DEVICE_2_OUTPUT_UPPER_LIM:n

R4

Device output upper limit. Read only.

85.112:n

HART.DEVICE_2_OUTPUT_LOWER_LIM:n

R4

Device output lower limit. Read only.

85.113:n

HART.DEVICE_2_DAMPING_VALUE:n

R4

Device damping value. Read only.

85.114:n

HART.DEVICE_3_POLL_MODE:n

UI1

The polling mode for the device.  0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update.

85.115:n

HART.DEVICE_3_POLL_ADDRESS:n

UI1

Polling address for the device. Read only.

85.116:n

HART.DEVICE_3_STATUS:n

UI1

0=no device found, 1=communication, 2=comm error.

85.117:n

HART.DEVICE_3_ACTUAL_SCAN_PERIOD:n

R4

Period at which device is being updates.

85.118:n

HART. DEVICE_3_TAG:n

STRING

10 character tag that resides in this device. Read only.

85.119:n

HART.DEVICE_3_RESPONSE_CODE:n

UI2

Response code and status received from device. Read only.

85.120:n

HART.DEVICE_3_ACTIVE_ALARMS:n

UI1

Active alarms reported by device. Read only.

85.121:n

HART.DEVICE_3_CURRENT:n

R4

Current in milliamps. Read only.

85.122:n

HART.DEVICE_3_PERCENT_RANGE:n

R4

Percent of range reported by device. Read only.

85.123:n

HART.DEVICE_3_FAILSAFE_ENABLE:n

UI1

Enables the use of fail safe values for the dynamic variables when the unit resets.

85.124:n

HART.DEVICE_3_PV_UNITS:n

UI1

Units code for primary variable reported by device. Read only.

85.125:n

HART.DEVICE_3_PV:n

R4

Value of primary variable reported by device. Read only.

85.126:n

HART.DEVICE_3_PV_FAILSAFE:n

R4

Primary fail safe value for device.

85.127:n

HART.DEVICE_3_SV_UNITS:n

UI1

Units code for secondary variable reported by device. Read only.

85.128:n

HART.DEVICE_3_SV:n

R4

Value of secondary variable reported by device. Read only.

85.129:n

HART.DEVICE_3_SV_FAILSAFE:n

R4

Secondary fail safe value for device.

85.130:n

HART.DEVICE_3_TV_UNITS:n

UI1

Units code for tertiary variable reported by device. Read only.

85.131:n

HART.DEVICE_3_TV:n

R4

Value of tertiary variable reported by device. Read only.

85.132:n

HART.DEVICE_3_TV_FAILSAFE:n

R4

Tertiary fail safe value for device.

85.133:n

HART.DEVICE_3_FV_UNITS:n

UI1

Units code for fourth variable reported by device. Read only.

85.134:n

HART.DEVICE_3_FV:n

R4

Value of fourth variable reported by device. Read only.

85.135:n

HART.DEVICE_3_FV_FAILSAFE:n

R4

Fourth fail safe value for device.

85.136:n

HART.DEVICE_3_SLOT_0_ASSIGN:n

UI1

Slot 0 variable to request from device.

85.137:n

HART.DEVICE_3_SLOT_0_UNITS:n

UI1

Units of slot 0 variable to request from device. Read only.

85.138:n

HART.DEVICE_3_SLOT_0_VARIABLE:n

R4

Value of slot 0 variable requested from device.

85.139:n

HART.DEVICE_3_SLOT_1_ASSIGN:n

UI1

Slot 1 variable to request from device.

85.140:n

HART.DEVICE_3_SLOT_1_UNITS:n

UI1

Units of slot 1 variable to request from device. Read only.

85.141:n

HART.DEVICE_3_SLOT_1_VARIABLE:n

R4

Value of slot 1 variable requested from device.

85.142:n

HART.DEVICE_3_SLOT_2_ASSIGN:n

UI1

Slot 2 variable to request from device.

85.143:n

HART.DEVICE_3_SLOT_2_UNITS:n

UI1

Units of slot 2 variable to request from device. Read only. 

85.144:n

HART.DEVICE_3_SLOT_2_VARIABLE:n

R4

Value of slot 2 variable requested from device.

85.145:n

HART.DEVICE_3_SLOT_3_ASSIGN:n

UI1

Slot 3 variable to request from device.

85.146:n

HART.DEVICE_3_SLOT_3_UNITS:n

UI1

Units of slot 3 variable to request from device. Read only.

85.147:n

HART.DEVICE_3_SLOT_3_VARIABLE:n

R4

Value of slot 3 variable requested from device.

85.148:n

HART.DEVICE_3_MESSAGE:n

STRING

40 character device message. 

85.149:n

HART.DEVICE_3_DESCRIPTION:n

STRING

20 character device description. 

85.150:n

HART.DEVICE_3_MANU_ID:n

UI2

Device manufacture ID. Read only.

85.151:n

HART.DEVICE_3_SERIAL:n

UI4

Device serial number. Read only.

85.152:n

HART.DEVICE_3_ID_NUMBER:n

UI4

Device sensor units. Read only.

85.153:n

HART.DEVICE_3_SENSOR_UNITS:n

UI1

Device sensor units. Read only.

85.154:n

HART.DEVICE_3_SENSOR_UPPER_LIM:n

R4

Device sensor upper limit. Read only.

85.155:n

HART.DEVICE_3_SENSOR_LOWER_LIM:n

R4

Device sensor lower limit. Read only.

85.156:n

HART.DEVICE_3_MINIMUM_SPAN:n

R4

Device minimum sensor span. Read only.

85.157:n

HART.DEVICE_3_OUTPUT_UNITS:n

UI1

Device output units. Read only.

85.158:n

HART.DEVICE_3_OUTPUT_UPPER_LIM:n

R4

Device output upper limit. Read only.

85.159:n

HART.DEVICE_3_OUTPUT_LOWER_LIM:n

R4

Device output lower limit. Read only.

85.160:n

HART.DEVICE_3_DAMPING_VALUE:n

R4

Device damping value. Read only.

85.161:n

HART.DEVICE_4_POLL_MODE:n

UI1

The polling mode for the device.  0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update.

85.162:n

HART.DEVICE_4_POLL_ADDRESS:n

UI1

Polling address for the device. Read only.

85.163:n

HART.DEVICE_4_STATUS:n

UI1

0=no device found, 1=communication, 2=comm error.

85.164:n

HART.DEVICE_4_ACTUAL_SCAN_PERIOD:n

R4

Period at which device is being updates.

85.165:n

HART. DEVICE_4_TAG:n

STRING

10 character tag that resides in this device. Read only.

85.166:n

HART.DEVICE_4_RESPONSE_CODE:n

UI2

Response code and status received from device. Read only.

85.167:n

HART.DEVICE_4_ACTIVE_ALARMS:n

UI1

Active alarms reported by device. Read only.

85.168:n

HART.DEVICE_4_CURRENT:n

R4

Current in milliamps. Read only.

85.169:n

HART.DEVICE_4_PERCENT_RANGE:n

R4

Percent of range reported by device. Read only.

85.170:n

HART.DEVICE_4_FAILSAFE_ENABLE:n

UI1

Enables the use of fail safe values for the dynamic variables when the unit resets.

85.171:n

HART.DEVICE_4_PV_UNITS:n

UI1

Units code for primary variable reported by device. Read only.

85.172:n

HART.DEVICE_4_PV:n

R4

Value of primary variable reported by device. Read only.

85.173:n

HART.DEVICE_4_PV_FAILSAFE:n

R4

Primary fail safe value for device.

85.174:n

HART.DEVICE_4_SV_UNITS:n

UI1

Units code for secondary variable reported by device. Read only.

85.175:n

HART.DEVICE_4_SV:n

R4

Value of secondary variable reported by device. Read only.

85.176:n

HART.DEVICE_4_SV_FAILSAFE:n

R4

Secondary fail safe value for device.

85.177:n

HART.DEVICE_4_TV_UNITS:n

UI1

Units code for tertiary variable reported by device. Read only.

85.178:n

HART.DEVICE_4_TV:n

R4

Value of tertiary variable reported by device. Read only.

85.179:n

HART.DEVICE_4_TV_FAILSAFE:n

R4

Tertiary fail safe value for device.

85.180:n

HART.DEVICE_4_FV_UNITS:n

UI1

Units code for fourth variable reported by device. Read only.

85.181:n

HART.DEVICE_4_FV:n

R4

Value of fourth variable reported by device. Read only.

85.182:n

HART.DEVICE_4_FV_FAILSAFE:n

R4

Fourth fail safe value for device.

85.183:n

HART.DEVICE_4_SLOT_0_ASSIGN:n

UI1

Slot 0 variable to request from device.

85.184:n

HART.DEVICE_4_SLOT_0_UNITS:n

UI1

Units of slot 0 variable to request from device. Read only. 

85.185:n

HART.DEVICE_4_SLOT_0_VARIABLE:n

R4

Value of slot 0 variable requested from device.

85.186:n

HART.DEVICE_4_SLOT_1_ASSIGN:n

UI1

Slot 1 variable to request from device.

85.187:n

HART.DEVICE_4_SLOT_1_UNITS:n

UI1

Units of slot 1 variable to request from device.

Read only.

85.188:n

HART.DEVICE_4_SLOT_1_VARIABLE:n

R4

Value of slot 1 variable requested from device.

85.189:n

HART.DEVICE_4_SLOT_2_ASSIGN:n

UI1

Slot 2 variable to request from device.

85.190:n

HART.DEVICE_4_SLOT_2_UNITS:n

UI1

Units of slot 2 variable to request from device.

Read only.

85.191:n

HART.DEVICE_4_SLOT_2_VARIABLE:n

R4

Value of slot 2 variable requested from device.

85.192:n

HART.DEVICE_4_SLOT_3_ASSIGN:n

UI1

Slot 3 variable to request from device.

85.193:n

HART.DEVICE_4_SLOT_3_UNITS:n

UI1

Units of slot 3 variable to request from device.

Read only.

85.194:n

HART.DEVICE_4_SLOT_3_VARIABLE:n

R4

Value of slot 3 variable requested from device.

85.195:n

HART.DEVICE_4_MESSAGE:n

STRING

40 character device message. 

85.196:n

HART.DEVICE_4_DESCRIPTION:n

STRING

20 character device description. 

85.197:n

HART.DEVICE_4_MANU_ID:n

UI2

Device manufacture ID. Read only.

85.198:n

HART.DEVICE_4_SERIAL:n

UI4

Device serial number. Read only.

85.199:n

HART.DEVICE_4_ID_NUMBER:n

UI4

Device sensor units. Read only.

85.200:n

HART.DEVICE_4_SENSOR_UNITS:n

UI1

Device sensor units. Read only.

85.201:n

HART.DEVICE_4_SENSOR_UPPER_LIM:n

R4

Device sensor upper limit. Read only.

85.202:n

HART.DEVICE_4_SENSOR_LOWER_LIM:n

R4

Device sensor lower limit. Read only.

85.203:n

HART.DEVICE_4_MINIMUM_SPAN:n

R4

Device minimum sensor span. Read only.

85.204:n

HART.DEVICE_4_OUTPUT_UNITS:n

UI1

Device output units. Read only.

85.205:n

HART.DEVICE_4_OUTPUT_UPPER_LIM:n

R4

Device output upper limit. Read only. 

85.206:n

HART.DEVICE_4_OUTPUT_LOWER_LIM:n

R4

Device output lower limit. Read only.

85.207:n

HART.DEVICE_4_DAMPING_VALUE:n

R4

Device damping value. Read only.

85.208:n

HART.DEVICE_5_POLL_MODE:n

UI1

The polling mode for the device.  0=skip, 1=primary only, 2=all dynamic, 3=all slot, 4=full update.

85.209:n

HART.DEVICE_5_POLL_ADDRESS:n

UI1

Polling address for the device. Read only.

85.210:n

HART.DEVICE_5_STATUS:n

UI1

0=no device found, 1=communication, 2=comm error.

85.211:n

HART.DEVICE_5_ACTUAL_SCAN_PERIOD:n

R4

Period at which device is being updates.

85.212:n

HART. DEVICE_5_TAG:n

STRING

10 character tag that resides in this device. Read only.

85.213:n

HART.DEVICE_5_RESPONSE_CODE:n

UI2

Response code and status received from device. Read only.

85.214:n

HART.DEVICE_5_ACTIVE_ALARMS:n

UI1

Active alarms reported by device. Read only.

85.215:n

HART.DEVICE_5_CURRENT:n

R4

Current in milliamps. Read only.

85.216:n

HART.DEVICE_5_PERCENT_RANGE:n

R4

Percent of range reported by device. Read only.

85.217:n

HART.DEVICE_5_FAILSAFE_ENABLE:n

UI1

Enables the use of fail safe values for the dynamic variables when the unit resets.

85.218:n

HART.DEVICE_5_PV_UNITS:n

UI1

Units code for primary variable reported by device. Read only.

85.219:n

HART.DEVICE_5_PV:n

R4

Value of primary variable reported by device. Read only.

85.220:n

HART.DEVICE_5_PV_FAILSAFE:n

R4

Primary fail safe value for device.

85.221:n

HART.DEVICE_5_SV_UNITS:n

UI1

Units code for secondary variable reported by device. Read only.

85.222:n

HART.DEVICE_5_SV:n

R4

Value of secondary variable reported by device. Read only.

85.223:n

HART.DEVICE_5_SV_FAILSAFE:n

R4

Secondary fail safe value for device.

85.224:n

HART.DEVICE_5_TV_UNITS:n

UI1

Units code for tertiary variable reported by device. Read only.

85.225:n

HART.DEVICE_5_TV:n

R4

Value of tertiary variable reported by device. Read only. 

85.226:n

HART.DEVICE_5_TV_FAILSAFE:n

R4

Tertiary fail safe value for device.

85.227:n

HART.DEVICE_5_FV_UNITS:n

UI1

Units code for fourth variable reported by device. Read only.

85.228:n

HART.DEVICE_5_FV:n

R4

Value of fourth variable reported by device. Read only.

85.229:n

HART.DEVICE_5_FV_FAILSAFE:n

R4

Fourth fail safe value for device.

85.230:n

HART.DEVICE_5_SLOT_0_ASSIGN:n

UI1

Slot 0 variable to request from device.

85.231:n

HART.DEVICE_5_SLOT_0_UNITS:n

UI1

Units of slot 0 variable to request from device. Read only.

85.232:n

HART.DEVICE_5_SLOT_0_VARIABLE:n

R4

Value of slot 0 variable requested from device.

85.233:n

HART.DEVICE_5_SLOT_1_ASSIGN:n

UI1

Slot 1 variable to request from device.

85.234:n

HART.DEVICE_5_SLOT_1_UNITS:n

UI1

Units of slot 1 variable to request from device. Read only.

85.235:n

HART.DEVICE_5_SLOT_1_VARIABLE:n

R4

Value of slot 1 variable requested from device.

85.236:n

HART.DEVICE_5_SLOT_2_ASSIGN:n

UI1

Slot 2 variable to request from device.

85.237:n

HART.DEVICE_5_SLOT_2_UNITS:n

UI1

Units of slot 2 variable to request from device. Read only.

85.238:n

HART.DEVICE_5_SLOT_2_VARIABLE:n

R4

Value of slot 2 variable requested from device.

85.239:n

HART.DEVICE_5_SLOT_3_ASSIGN:n

UI1

Slot 3 variable to request from device.

85.240:n

HART.DEVICE_5_SLOT_3_UNITS:n

UI1

Units of slot 3 variable to request from device. Read only.

85.241:n

HART.DEVICE_5_SLOT_3_VARIABLE:n

R4

Value of slot 3 variable requested from device.

85.242:n

HART.DEVICE_5_MESSAGE:n

STRING

40 character device message. 

85.243:n

HART.DEVICE_5_DESCRIPTION:n

STRING

20 character device description. 

85.244:n

HART.DEVICE_5_MANU_ID:n

UI2

Device manufacture ID. Read only.

85.245:n

HART.DEVICE_5_SERIAL:n

UI4

Device serial number. Read only.

85.246:n

HART.DEVICE_5_ID_NUMBER:n

UI4

Device sensor units. Read only.

85.247:n

HART.DEVICE_5_SENSOR_UNITS:n

UI1

Device sensor units. Read only.

85.248:n

HART.DEVICE_5_SENSOR_UPPER_LIM:n

R4

Device sensor upper limit. Read only.

85.249:n

HART.DEVICE_5_SENSOR_LOWER_LIM:n

R4

Device sensor lower limit. Read only.

85.250:n

HART.DEVICE_5_MINIMUM_SPAN:n

R4

Device minimum sensor span. Read only.

85.251:n

HART.DEVICE_5_OUTPUT_UNITS:n

UI1

Device output units. Read only.

85.252:n

HART.DEVICE_5_OUTPUT_UPPER_LIM:n

R4

Device output upper limit. Read only.

85.253:n

HART.DEVICE_5_OUTPUT_LOWER_LIM:n

R4

Device output lower limit. Read only.

85.254:n

HART.DEVICE_5_DAMPING_VALUE:n

R4

Device damping value. Read only.

85.255:n


Point Type 91 - System Items  

ItemData TypeDescriptionT.P:L

SYSTEM.ROC_UNIT or SYSTEM.ROC_ADDRESS

UINT8

One-byte unit code of the station address. The unit code for a ROC address is configurable by the user. A 0 is used for broadcast.

91.0:n

SYSTEM.ROC_GROUP

UINT8

Group code of the station address.

91.1:n

SYSTEM.STATION_NAME

AC

A 20-character ASCII field for the station name.

91.2:n

SYSTEM.PART_VERSION

AC

Contains the software part number and version number string. READ ONLY.

91.3:n

SYSTEM.TIME_CREATED

AC

Contains the time and date stamp the firmware was created. READ ONLY.

91.4:n

SYSTEM.MANU_ID

AC

Contains manufacturing identification string. READ ONLY.

91.5:n

SYSTEM.PROD_DESCRIPTION

AC

Contains manufacturing description of product. READ ONLY.

91.6:n

SYSTEM.SERIAL_NUMBER

UINT32

Contains the serial number for the unit.  READ ONLY.

91.7:n

SYSTEM.MAX_EVENTS or SYSTEM.ROM_EVENTS

UINT16

Contains the maximum number of events that the Event Log may contain. READ ONLY.

91.8:n

SYSTEM.MAX_ALARMS or SYSTEM.ROM_ALARMS

UINT16

Contains the maximum number of alarms that the Alarm Log may contain. READ ONLY.

91.9:n

SYSTEM.MAX_PIDS or SYSTEM.ROM_PIDS 

UINT8

Contains the maximum number of PID loops that may run on the system. READ ONLY.

91.10:n

SYSTEM.MAX_AGAS or SYSTEM.ROM_AGAS

UINT8

Contains the maximum number of Meter Runs that may run on the system. READ ONLY. 

91.11:n

SYSTEM.MAX_FST or SYSTEM.ROM_FST

UINT8

Contains the maximum number of FSTs that may run on the system. READ ONLY.

91.12:n

SYSTEM.EVENT_INDEX

UINT16

Indicates the current event index in the Event Log. READ ONLY.

91.13:n

SYSTEM.ALARM_INDEX

UINT16

Indicates the current alarm index in the Alarm Log. READ ONLY.

91.14:n

SYSTEM.ACTIVE_PIDS

UINT8

Number of active PIDs

91.15:n

SYSTEM.ACTIVE_STATIONS

UINT8

Number of active stations.

91.16:n

SYSTEM.ACTIVE_ORIFICE

UINT8

Number of active orifice meter runs.

91.17:n

SYSTEM.ACTIVE_TURBINE

UINT8

Number of active turbine meter runs.

91.18:n

SYSTEM.FST_CLEAR

UINT8

Setting this parameter clears FST code from Flash ROM. 

•       0 – Does nothing. 

•       1 – Initiates clearing of FST code.

91.19:n

SYSTEM.CLEAR_CONFIG

UINT8

Used to clear the internal configuration memory stored in flash ROM.

•       0 = Do nothing

•       1 = Enable clearing of Configuration Memory

91.20:n

SYSTEM.WRITE_CONFIG

UINT8

Used to command the ROC to store certain point types (indicated throughout this document) to flash configuration memory

•       0 = Do nothing

•       1 = Perform Write to Configuration Memory

91.21:n

SYSTEM.WRITE_COMPLETE

UINT8

Used to indicate that the system is the process of writing the configuration to flash ROM

•       0 = Currently Performing the Write

•       1 = Completed the Write

READ ONLY.

91.22:n

SYSTEM.MPU_LOADING

FLP

Contains the current percentage of time the CPU is being loaded, updated every 5 seconds. READ ONLY.

91.23:n

SYSTEM.RESERVED

UINT8

Unused parameter. READ ONLY.

91.24:n

SYSTEM.IO_SCANNING

UINT8

Used to enable or disable scanning of all I/O in the system.

•       0 = Disabled

•       1 = Enabled

91.25:n

SYSTEM.WARM_START

UINT8

Used to re-start the system. A warm start is a reboot of the system without performing all the power-on-self tests.

•       0 = Do nothing

•       1 = Perform Warm Start

91.26:n

SYSTEM.COLD_START

UINT8

Used to re-start the system. A cold start always includes starting from the boot sector and performing power-on-self tests, plus the following options.

•       0 = Do nothing

•       1 = Restore Configuration from Flash

•       2 = Clear Alarms

•       3 = Clear Events

•       4 = Clear FSTs

•       5 = Clear History & Meter Runs

•       6 = Restore Configuration from Flash, Clear Alarms/Events/FST’s/History/Meter Runs

•       7 = Restore Configuration from Defaults

91.27:n

SYSTEM.LCD_INSTALLED

UINT8

•       0 = No LCD installed or LCD is disabled

•       1 = LCD installed and enabled READ ONLY.

91.28:n

SYSTEM.LCD_POWERSAVE

UINT8

Enables or disables the power saving feature of the LCD.

When enabled the display will stay on until the power off time expires. 0 – Disable Power Saving,  1 – Enable Power Saving.

Note: Since this functionality has not yet be added to the firmware (as of Version 1.00) this parameter is currently R/O. When the functionality is added, it will be made R/W.

91.29:n

SYSTEM.LCD_OWNER

UINT8

The current owner of the LCD. This is used if a user C program is needed to run the LCD.

•       0 = LCD

•       1 = User C Program 1

•       2 = User C Program 2

•       3 = User C Program 3

•       4 = User C Program 4

•       5 = User C Program 5

•       6 = User C Program 6

•       7 = User C Program 7

•       8 = User C Program 8

91.30:n

SYSTEM.BAUD_RATE_0

UINT32

The baud rate that baud rate generator #0 is to be set to.

91.31:n

SYSTEM.BAUD_RATE_1

UINT32

The baud rate that baud rate generator #1 is to be set to.

91.32:n

SYSTEM.BAUD_RATE_2

UINT32

The baud rate that baud rate generator #2 is to be set to.

91.33:n

SYSTEM.BAUD_RATE_3

UINT32

The baud rate that baud rate generator #3 is to be set to.

91.34:n

SYSTEM.CRC_CHECK

UINT8

The CRC check flag. If this flag is enabled, a CRC will be appended to all messages and a CRC will be expected on all received messages. Disabled = 0, Enabled = 1.

91.35:n

SYSTEM.LED_ENABLE

UINT8

Indicates the number of minutes the LEDs will be on before automatically turning themselves off. (The LED buttons will active the LEDs for the configured time).

•       0 = LEDs always on

•       1 - 60 = Number of minutes LEDs will be on

91.36:n

SYSTEM.BOOT_PART_NUM

AC

Contains the boot software part number and version number string. READ ONLY.

91.37:n

SYSTEM.BOOT_FIRMWARE_TIME

AC

Contains the time and date stamp the boot firmware was created. READ ONLY.

91.38:n

SYSTEM.ACTIVE_ODORIZERS

UINT8

Number of active odorizers

91.39:n

SYSTEM.CLEAR_HISTORY_CONFIG

  

Clears history database and resets configuration back to factory defaults without power cycling the ROC.

Don't clear = 0, Clear = 1.

91.40:n

...

ItemData TypeDescription

GCWrite/Txn

Variant Array

Used for automated gas quality download. 

LastAlarmRecord/n

Date

Timestamp of the last alarm record retrieved from meter number 'n'.  

LastDailyRecord/n

Date

Timestamp of the last daily record retrieved from meter number 'n'.  

LastEventRecord/n

Date

Timestamp of the last event record retrieved from meter number 'n'.  

LastHourlyRecord/n

Date

Timestamp of the last hourly record retrieved from meter number 'n'.  

ClockSetDateSet the Date and Time on the device.

LastTimeSync

Date

Timestamp of the last time synchronization attempt.  

LastTimeSyncResult

I4

Result of the last time synchronization attempt. 

MoveDaily

I2

Move the daily history retrieval pointer for meter run 1. Write a positive number to move the pointer back in time, a negative number to move the pointer forward in time. The written value represents the number of days to move. 

MoveHourly

I2

Move the hourly history retrieval pointer for meter run 1. Write a positive number to move the pointer back in time, a negative number to move the pointer forward in time. The written value represents the number of hours to move. 

Reinitialize

I2

Re-read the ROC configuration

ResetAlarm

BOOL

Erase the Alarm history retrieval pointer for meter 1 all meters (and recollect all Alarm history during the next retrieval). 

ResetDaily

BOOL

Erase the daily history retrieval pointer for meter 1 all meters (and recollect all daily history during the next retrieval). 

ResetEvent

BOOL

Erase the event history retrieval pointer for meter 1 all meters (and recollect all event history during the next retrieval). 

ResetHourly

BOOL

Erase the hourly history retrieval pointer for meter 1 all meters (and recollect all hourly history during the next retrieval). 

RetrieveHistory

I2

Retrieve enabled history.

RetrieveMeterConfiguration

I2

Retrieve enabled Meter Configuration.

SkipDaily

I2

Skip enabled history

SkipHourly

I2

Skip enabled history

TimeSync

I2

Perform time synchronization.

...