Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 13 Next »

Overview

The Alias Group object allows custom item names to be linked to protocol item names. This is particularly useful with numeric item names. 

Alias Items and Groups

To create an alias for use at the $Server level for register 5176 which is "Mass" for the Modbus Omni Protocol, the Alias Name would be entered as ‘ModbusOmniDevice.Mass’ (including the device name), and the corresponding item name would be entered as ‘ModbusOmniDevice.5176’ (also including the device name). Server level alias groups are created on the Aliasing tab of the $Server object.

An alias group can also be created for use with a single device or can be created for a group of devices of the same protocol if the tags are the same.  

Alias item names at the device/protocol level MUST NOT include the device name, only the item name. 

Using the same example as above, an alias name at the device/protocol level would be entered as ‘Mass’, and the corresponding item name would be entered as ‘5176’. An OPC Client that wanted the Mass value from the device named ModbusOmniDevice would use an OPC item named ‘ModbusOmniDevice.Mass’.

Item Modifiers

Item modifiers and item scaling can be used in alias groups, with the modifier will be appended to the item name and NOT the alias name. For example if the raw value returned for Mass is 2500 and the scaled value should be .25, the alias name might be entered as ‘Scaled Mass’ and the item name would be entered as ‘5176{SG:.001,0}’.  For more information on item scaling, please see Item Scaling section.

Configuration

General Tab

See General Object Configuration page.

Alias Records


Edit Records

Click the Edit Records button to open the Alias Record Collection dialog box to add the alias names and item names.

Click Add to enter the appropriate number of New Record items.

Click Remove to delete any unwanted New Record items.

Click Tabular Display to view all New Record items at once.

Alias Name

The name by which the item will be referenced.  Max Length: 255 characters.

Item Name

The item name of the point in the device.  Modifiers and scaling can appended to the Item Name.  Max Length: 255 characters.

Record Id

Used to describe this entry.  Max Length: 50 characters.

Saving Record Collection Changes

When record editing is complete, Click Close to return to the owning object type. Click the Save button  to save any changes made to the record collection.

Options

Output Destinations

All items in the alias group are sent collectively to the selected destination..  

     ACM Mobile: Sends the items to ACM Mobile app user

     Auto Poll: Activate the items internally without waiting for a client to connect and activate them. This is only available if MQTT or ACM Mobile option is not selected.

Interval

This is the schedule interval that is applied to the items in the alias group.


  • No labels