GE SRTP

GE SRTP

Introduction

A driver for GE PLCs that support the SRTP protocol, full ACM writeup here: https://autosoln.atlassian.net/wiki/x/LYRsD

Tabs

General

image-20251127-195217.png

Property

Description

Property

Description

Name

The name of this GE SRTP Protocol object. The name is used when data is published.

Description

A note field for information about the device

Enabled

If checked, Edge ACM will poll this device when running

Bytes Per Reference Request

Default = 2048. This setting restricts the maximum number of bytes per message during reference (‘%’) value reads. If you request more bytes than specified here then the request will be split into multiple poll messages.

The only reason to adjust this setting is if you are getting consistent timeouts on a slow connection due to message size.

Symbolic Variable Metadata Request Per Message

Default = 100. Max number of symbolic variable metadata items to resolve per message.

Symbolic Variable Value Request Bytes Per Message

Default = 1024. Max number of symbolic variable value bytes to request per message.

Symbolic Variable Value Request Count Per Message

Default = 500. Max count of symbolic variable values to request per message.

Tag Groups

The Tag Groups that are associated with this device. Edge ACM will only poll this device for the tags in the groups selected here

Connection Settings

The object that contains the connection settings Edge ACM will use to connect to the End Device

Folder

The parent folder for this item

Advanced

image-20251127-203654.png

It is recommended that the advanced values not be changed unless advised by technical support to do so.

Property

Description

Property

Description

Destination Node

Default = 3600.

Symbolic Variable Pathname

Default = Not selected. This setting is only used when Override Retrieved Symbolic Variable Pathname with Manual Setting in Protocol Options is checked.

Override Retrieved Symbolic Variable Pathname with Manual Setting

Default = Not selected. Selecting this will use the entry in the Symbolic Variable Pathname property for the protocol’s symbolic variable handle and metadata read messages.

Use Verbose Logging

Default = Not selected. Selecting this will turn on more verbose logging during symbolic variable reads. This is useful when needing more information to diagnose issues with polling for symbolic variables and other similar situations. 

Comm Stats

See the Comm Stats entry on the Common Tabs page: Common Tabs | Comm Stats

For assistance, please submit a ticket via our Support Portal, email autosol.support@autosoln.com or call 281.286.6017 to speak to a support team member.