DNP3

DNP3

Documentation for the converted driver from ACM can be found here: https://autosoln.atlassian.net/wiki/x/n4FsD

General

image-20251127-210825.png

Property

Description

Property

Description

Name

The name of this GE SRTP Protocol object. The name is used when data is published.

Description

A note field for information about the device

Enabled

If checked, Edge ACM will poll this device when running

Primary/Secondary Destination Address

Default = 0. The address that eACM will use as the device's address in DNP3 messages.

Primary/Secondary Source Address

Default = 0. The address that eACM will use as its own address in DNP3 messages.

Protocol Options

  • No class zero poll to initialize items

    • Default = Not selected. By default, a class 0 poll is sent to initialize class 1-3 items upon activation. Select this option to not send the class 0 initialization poll.

  • No data integrity check in demand poll

    • Default = Not selected. The data integrity check item sends a class 0 poll that updates all class 1-3 items. By default, this will be done both on interval and as part of any demand poll that includes the data integrity check item. Select this option to not send the class 0 data integrity check poll in a demand poll.

  • Use select-operate for control writes

    • Default = Not selected. By default, control writes are performed using the direct operate command. Some devices, such as the Emerson FBx, don't support direct operate control writes.  Select this option to use the select-operate command instead.

  • Initialize class 1-3 after comm fail

    • Default = Not selected. Class 1-3 polls only return values for items that have changed since the previous class 1-3 poll. Because of this, if class 1-3 items are invalidated after a communication failure, by default they will not become valid again until their value changes in the device. Select this option to send a class 0 poll to initialize the class 1-3 items after a communication failure, so that all class 1-3 items will become valid again immediately once communication is restored.

Tag Groups

The Tag Group(s) that are associated with this device. Edge ACM will only poll this device for the tags in the groups selected here

Connection Settings

The object that contains the connection settings Edge ACM will use to connect to the End Device

Folder

The parent folder for this item

Logging

See the Logging entry on the Common Tabs page: Common Tabs | Logging

Comm Stats

See the Comm Stats entry on the Common Tabs page: Common Tabs | Comm Stats

Time Sync

See the Time Sync entry on the Common Tabs page: Common Tabs | Time Sync

For assistance, please submit a ticket via our Support Portal, email autosol.support@autosoln.com or call 281.286.6017 to speak to a support team member.