Allen-Bradley® Protocols

Overview

ACM supports communication with both legacy Allen-Bradley® Ethernet and Serial devices via the DF1 Protocol as well as newer Common Industry Protocol (CIP) based devices using the ControlLogix protocol. 

Protocol Selection Table

Device TypeCommunicating ThroughProtocol (ACM)Notes

MicroLogix® 1000

MicroLogix® 1200

1774-PLC

PLC-2

SLC-500

SLC-5/03/04

SerialDF1Uses classic DF1 addressing scheme

PLC-5

SLC-5/05

Serial/*EthernetDF1

See DF1 Over Ethernet

*Ethernet communication mode requires specific configuration settings on the device object.

MicroLogix® 1100

MicroLogix® 1400

MicroLogix® 1500

Serial/*EthernetDF1

See DF1 Over Ethernet

*Ethernet communication mode requires specific configuration settings on the device object.

CompactLogix®EthernetControlLogixTag based addressing with tag catalog discovery.
CompactLogix®Serial(Processor Port)DF1Uses classic DF1 addressing scheme.
ControlLogix® 1756EthernetControlLogixTag based addressing with tag catalog discovery.
ControlLogix® 1756Serial (Processor Port)DF1Uses classic DF1 addressing scheme.

Information

In general, the DF1 protocol should be used unless the device specifically adheres to the Logix5000® series CIP communication standard.

Supported Protocols

ControlLogix

DF1

For assistance, please submit a ticket via our Support Portal, email autosol.support@autosoln.com or call 281.286.6017 to speak to a support team member.