GC Write Override Tab
The GC Write tab allows users to configure which TLPs are written to upon gas chromatograph write events.
Configuring GC Write override is optional. If you do not configure GC Write overrides here, the ROC protocol will default to the following TLPs:
Component | ROC 800 Gas Meters | ROC800 Liquid Meters | All other Gas Meters |
---|---|---|---|
METHANE | 112.28 | 203.105 | 7.28 |
ETHANE | 112.29 | 203.106 | 7.29 |
PROPANE | 112.30 | 203.107 | 7.30 |
IBUTANE | 112.32 | 203.109 | 7.32 |
NBUTANE | 112.31 | 203.108 | 7.31 |
IPENTANE | 112.34 | 203.111 | 7.34 |
NPENTANE | 112.33 | 203.110 | 7.33 |
NEOPENTANE | N/A | 203.104 | N/A |
NHEXANE | 112.35 | 203.112 | 7.35 |
NHEPTANE | 112.36 | 203.113 | 7.36 |
NOCTANE | 112.37 | 203.104 | 7.37 |
NDECANE | 112.39 | 203.126 | 7.39 |
C6PLUS | 112.47 | N/A | N/A |
H2 | 112.45 | N/A | 7.42 |
H2O | 112.41 | 203.128 | 7.26 |
H2S | 112.40 | 203.120 | 7.25 |
O2 | 112.43 | 203.118 | 7.40 |
CO | 112.44 | N/A | 7.41 |
CO2 | 112.27 | 203.119 | 7.24 |
N2 | 112.26 | 203.117 | 7.23 |
HELIUM | 112.42 | 203.127 | 7.27 |
ARGON | N/A | N/A | N/A |
BTU | 112.22 | N/A | 7.6 |
SPECIFICGRAVITY | 112.23 | N/A | 7.5 |
USERDEFINEDSTRING1 | N/A | N/A | N/A |
USERDEFINEDSTRING2 | N/A | N/A | N/A |
USERDEFINEDDOUBLE1 | N/A | 201.8 | N/A |
USERDEFINEDDOUBLE2 | N/A | N/A | N/A |
USERSTRING | N/A | N/A | N/A |
If you do link a Gas Chromatograph object for a specific meter and you wish to override the default TLP that is written to for a specific component, you must be explicit which TLP you would like to write to. In the example below, for the meter in question, when the user or system sends a USERDEFINEDDOUBLE1 value, that value will be written to the soft point 98.3:4. Since all the other component entries in that Gas Chromatograph object example are empty, they will default to the TLP as defined in the table above.