Configuration

...

Property

Description

Name

The name of this item

Enabled

If checked the , Edge ACM will poll this device when running

ROC Series

The type of ROC you wish to poll:

  • Floboss 100 Series & FBx

  • Floboss 503

  • Floboss 504

  • REGFLO

  • ROC 300 ROCPAC

  • ROC 300 FLASHPAC

  • ROC 407

  • ROC 800 Series

Industry Canada ROC

Indicates that the device has been configured to Industry Canada standards

Publish Rate

The time, in milliseconds, between Device Data Messages

Alter Publish Rate on Point Limits

If enabled, tag limits are monitored by the publisher and the publisher will switch to the Altered Publish Rate if any tag is out of limits

Altered Publish Rate

The time, in milliseconds, between Device Data Messages if any tags assigned to this device are out of limits (Limits are set on the tag object)

ROC Unit

Sets the ROC Unit Address, valid values 0-255

ROC Group

Sets the ROC Group Address, valid values 0-255

Host Unit

Sets the Host Unit Address, valid values 0-255

Host Group

Sets the Host Group Address, valid values 0-255

Max Message Length

Sets a limit on the maximum number of bytes to send in a single message to the End Device, valid values 8-240

Read User Opcode Data Via Opcode 10

This option causes eACM to read user opcode points using ROC protocol opcode 10 instead of opcode 180.  This can be a more efficient way to read user opcode points, as long most of the requested points are continuous.  If there are many gaps between requested user opcode points, then this option may not be desirable, as gaps will cause items to be polled in separate reads.  This option is sometimes required to read user opcode data sourced from a user program running the ROC device that cannot be read with opcode 180

Tag Groups

The Tag Groups that are associated with this device. Edge ACM will only poll this device for the tags in the groups highlighted selected here

Connection Settings

The object that contains the connection settings Edge ACM will use to connect to the End Device

Folder

The parent folder for this item

Comm Stats

...

Items available for publishing:

Property

Description

Internal Tags Publishing Group

An integer ID (0-255) that can be used to map the included Comm Stat tags in this device to a publish schedule.

Include Active Items tag

Publishes the ActiveItems tag which is a count of the total number of tags on this device.

Include Barometer tag

Publishes the Barometer indicator.

Note: The communications barometer represents the marginal success rate of communications. For each poll cycle that does not receive a response for one or more poll messages, the barometer will increase by two (2), with a maximum value of 100. For each poll cycle that does receive a valid response for all poll messages, the barometer to decreases by 1, with the lowest value being 0. These barometer changes cause failures in communications to show up quickly as the barometer rises. However, good communications must be maintained longer and more steadily for the barometer to fall back to 0.

Include Comm Status tag

Publishes the CommStatus tag which represents the status of the communication link to the device. The value will be 1 if a communication link to the device can be established – even if the device does not respond to polls. The value will be 0 if a communication link cannot be established to the device.

Include Demand tag

Publishes the Demand tag which, when written to, will trigger an out of schedule poll of all tags on the device.

Include Incomplete Poll tag

Publishes the IncompletePoll tag which is set to false at the beginning of each poll. The value changes from false to true if the last poll attempt was incomplete.

Include Last Poll Attempt Time tag

Publishes the LastPollAttemptTime tag which is updated with the date time stamp of the last poll attempt in UTC (without time zone bias).

Include Last Poll Failure Code tag

Publishes the LastPollFailureCode tag which is updated with an integer value indicating the result of the last poll.

  • 0 = Success

  • 1 = No poll initiated

  • 2 = Error opening connection

  • 3 = Error during modem initialization

  • 4 = Connection failed

  • 5 = Line is busy

  • 6 = No answer

  • 7 = Connection was dropped

Include Last Poll Length tag

Publishes the LastPollLength tag which is updated with the length (in bytes) of the last poll message sent to a device.

Include Last Poll Success Time

Publishes the LastPollSuccessTime tag which is updated with the date time stamp of the last successful poll in UTC (without time zone bias).

Include Seconds Since Complete

Publishes the SecondsSinceComplete tag which is updated with the seconds since the last complete poll.